M4M 20
NETWORK ANALYZER USER MANUAL
35
7.7.Lock MID version
At the end of the “7.First commissioning” phase the lock operation is required. It can be set once and the
user cannot reset the lock state.
M4M 20-M will not count any MID energy until it is locked.
M4M 20-M (MID) only
Following parameters, set during first commissioning phase,
cannot be modified after the lock
operation.
• Primary current transformer
• Secondary current transformer
• Primary voltage transformer
• Secondary voltage transformer
• Type of network settings
Summary of Contents for M4M 20
Page 1: ...Network analyzer M4M 20 M4M 20 M User manual M4M 20 User manual 2CSG445032D0201 ...
Page 2: ......
Page 67: ... ...