L ST4 0 0 |
U LT R A S O N I C L E V EL T R A N SM I T T ER
| O I/L S T4 0 0 - EN R E V. E
8
5 Configuration distance / level
DISTANCE / LEVEL MODE
BASIC
OPTIONS
DEFAULTS
SECURITY CODE
0-9999
5159
MODE
DISTANCE/LEVEL/FLOW/DIFF
DISTANCE
UNITS
FEET/METERS
FEET
EMPTY DISTANCE
1.3-49.2/3.6-98.4/3.6-196.8 FT
32.81 FT
SPAN
0.33-49.2/0.33-98.4/0.33-196.8 FT
32.81 FT
BLANKING
0.98-48.87/3.28-98.07/3.28-196.47 FT
1.65 FT
RATE OF CHANGE
0.03-65.6 FT/MIN / 0.01-20.0 M/MIN
3.28 FT/MIN
APPLICATION
LIQUIDS/SOLIDS
LIQUIDS
FACTORY RESET
NO/YES
NO
TEMPERATURE COMPENSATION
OFF/ON
OFF
SIMULATE
NO/YES
NO
SET PASSWORD
NO/YES
NO
BACKLIGHT
OFF/ON (1-6MIN)/PERM
2MIN
LOSSTIME
30-900SEC
300SEC
FAILSAFE
3.6mA, 4.0mA, 20mA, 21mA, HOLD
HOLD
ENGINEERING UNITS
NONE, aaa-zzz, AAA-ZZZ, 0-9
NONE
MAXIMUM VALUE
0-99999
100000
DECIMAL POINT
0-3
2
ZERO OFF SET
-0.16 FT TO 0.16 FT
0
SETUP RELAYS
NO/YES
NO
RELAY1 TO RELAY 5
OFF/LO/HI
OFF
CHANNEL SELECT
ONE/TWO/BOTH
ONE
SETPOINT
SPAN
1.65 FT
PUMP CYCLE
OFF/FIFO/ROTATE
OFF
CLEAR RELAYS
NO/YES
NO
SETUP LINEARIZER
NO/YES
NO
ACTIVATE LINEARIZER
NO/YES
NO
SETPOINT
1-21
1
HEIGHT
0 FT-SPAN
0 FT
PERCENTAGE
0-100%
0%