3 Calibration
3.14. Fine calibration procedure on TPU
65
3HAC 022907-001 Revision: -
3.14. Fine calibration procedure on TPU
General
This section details how to use the Teach Pendant Unit (TPU) when performing a fine
calibration of the robot. The method of fitting the calibration equipment to each axis is
detailed in the calibration instruction for the axis.
Fine calibration procedure
Step
Action
Note/Illustration
1.
Press the button
"Miscellaneous".
xx0100000194
2.
Select the
Service
window by pressing
ENTER.
xx0100000200
3.
Select
Calibration
from the
View
menu.
The Calibration window
appears.
If multiple units are
connected to the robot,
they will be listed in the
window.
xx0100000201
The calibration status can be any of the following:
•
Synchronized: all axes are calibrated and their
positions are known. The unit is ready for use.
•
Revolution Counter not updated: all axes are
fine-calibrated but one (or more) of the axes has
a counter that is NOT updated. This axis, or
these axes, must therefore be updated as
detailed in section
•
Not calibrated: one (or more) of the axes is NOT
fine-calibrated. This axis, or these axes, must
therefore be fine-calibrated as detailed below
and in the calibration instructions for each axis.
Summary of Contents for Levelmeter 2000
Page 2: ......
Page 6: ...Table of Contents 3HAC 022907 001 Revision 4...
Page 8: ...Overview 3HAC 022907 001 Revision 6...
Page 14: ...1 Overview 1 4 Calibration movement directions for all axes 3HAC 022907 001 Revision 12...
Page 78: ...3 Calibration 3 17 Updating revolution counters 3HAC 022907 001 Revision 76...
Page 82: ......