3 Calibration
3.8. Calibration, axis 1, IRB 6400R
51
3HAC 022907-001 Revision: -
6.
Fit the calibration tool (C) over the measuring pin
and the calibration fixture.
If the tool fits over the pin and the fixture
simultaneously, axis 1 is calibrated correctly. If
not, manually run axis 1 with the joystick until the
tool may be fitted over both the pin and the
fixture.
Art. no. is specified in
xx0400001129
7.
Update only axis 1.
Detailed in sections:
Fine calibration procedure on
TPU
on page 65 (RobotWare
4.0).
Fine calibration procedure on
FlexPendant
(RobotWare 5.0).
8.
Remove the calibration tools from axis 1.
Step
Action
Note