background image

IB 6.2.11.1-1C 

Page 14 

ABB 

 

Circuit Breaker Removal 

 
To move the circuit breaker to the TEST position or to 
remove it from the compartment, proceed as follows: 
 
1.  On electrically operated (EO) models, turn the motor 
disconnect switch to the OFF position. 
 
2. With the compartment door closed, trip the circuit 
breaker by means of the remote mounted control 
switch or manual TRlP button on the escutcheon. 
 
3. Lift the racking shutter, insert the racking crank and 
turn counterclockwise until the position indicator on the 
right-hand side of the escutcheon shows TEST 
position.  (NOTE: The circuit breaker may be tested in 
this position;  the primary contacts are disconnected 
and the control contacts are connected.) 
 
4. Continue turning the racking crank counterclockwise 
until the position indicator on the right-hand side of the 
escutcheon shows DISCONNECTED position. 
 
5. The circuit breaker may not be racked out with the 
closing springs charged.  At a point between the 
DISCONNECTED and OUT positions, the closing 
springs will automatically discharge. 
 
6. Rack the circuit breaker through the DISCONNECT 
position to the OUT position.  Rack the circuit breaker 
as far as the stops will allow but DO NOT FORCE.  
Open the cubicle door. 
 
7. Pull circuit breaker forward until tracks are in the fully 
extended and latched position. 
 
8. Using a lifting yoke, just pick up the circuit breaker 
weight. 
 
9. Lift the pivoting latches on the sides of the breaker, 
and pull the breaker forward to release the positioning 
pins from the cut-out sections of the tracks. 
 
10. Lift the circuit breaker free from the tracks. 
 
11. Release latch on each track, push tracks into the 
compartment, and close compartment door. 
 
 

MAINTENANCE AND INSPECTION 

 

Safety Notes 

 
De-energize both primary circuits and secondary 
control circuits before making any inspections, 
adjustments or parts replacements.  Check the OPEN/

CLOSED indicator for contact status and closing spring 
charge indicator for closing spring status. 
 
When it is necessary to charge the closing springs and/
or operate the circuit breaker during maintenance, keep 
hands and tools away from operating parts. 
 
Circuit breakers should be withdrawn to the TEST 
position for checking the breaker operation.  For further 
inspection, adjustments, cleaning, or parts 
replacement, the circuit breaker should be withdrawn 
and moved to a suitable work area. 
 

Periodic Maintenance Inspection 

 
The safety and successful functioning of downstream 
devices depends upon the proper operation of their 
feeder circuit breaker.  Therefore, a maintenance 
program should be established that will provide for 
periodic inspection of the circuit breaker as follows: 
 
KP-8, KPE-8, or KDP-8 - After 1,750 Operations 
KPH-8, KP-16, KPE-16, KDP-16 or KP-20 - After 500 
Operations 
 
Note: An operation counter is available as an option. 
 
The above inspection periods apply for no load or load 
current switching.  At the end of the first year of service 
the circuit breaker should be inspected regardless of 
the number of operations on it. 
 
If the total number of operations in service is very low, 
maintenance schedules should be based on time rather 
than operations; yearly inspections are advised.  When 
operations are low, moreover, mechanism exercising is 
important. 
 
The circuit breaker should always be inspected after 
short circuit or severe overload interruption, regardless 
of the time elapsed or number of operations since the 
last maintenance interval.  When the circuit breaker is 
used as a contactor, where it may be operated by 
automatic switching devices, the operations on it will 
accumulate more quickly necessitating more frequent 
inspection.  ANSI Standard C37.16 can provide 
additional information on this subject. 
 
Where unusual service conditions exist, it must be 
assumed that the conditions were considered at the 
time of order; that the equipment supplied was 
designated for the special application; and that an 
appropriate supplemental maintenance program has 
been developed.  Maintenance records containing the 
date of last inspection and the condition of the circuit 
breaker, as well as any adjustments or replacements 
made, should be filed as a guide for any special 

Summary of Contents for K-Line Plus KDP-16

Page 1: ...IB 6 2 11 1 1C Installation Maintenance Instructions Low Voltage Power Circuit Breaker K Line Plus Type KP 8 thru KP 20 ABB ...

Page 2: ...Representative CONTENTS PAGE INTRODUCTION 3 QUICK REFERENCE FOR UNCRATING INSPECTION AND INSTALLATION 3 CIRCUIT BREAKER ESCUTCHEON FEATURES 4 CIRCUIT BREAKER INTERNAL COMPONENTS 6 K LINE PLUS CIRCUIT BREAKER CRADLE FEATURES 7 SOLID STATE TRIP SYSTEM 8 OPERATING SEQUENCE FOR ELECTRICALLY OPERATED EO CIRCUIT BREAKERS 9 CLOSING SPRING OPERATION MO 10 INSTALLATION INITIAL TESTING AND REMOVAL 10 MAINTE...

Page 3: ...akers immediately upon receipt Examine shipping cartons to determine if any damage or loss was sustained during transit When such damage is evident file a damage claim with the carrier and notify your ABB sales office ABB is not responsible for damage of goods after delivery to the carrier but will assist when notified of claims The period of time after shipment that claims can be filed is short s...

Page 4: ... circuit breaker can be racked to the connected position using a procedure similar to 12 above CIRCUIT BREAKER ESCUTCHEON FEATURES The K Line Plus low voltage power circuit has a number of standard features and can be equipped with numerous other optional features Refer to Figure 1 as the features are discussed below Circuit Breaker Nameplates There are two nameplates on the circuit breaker The br...

Page 5: ...dle 9 OPEN or CLOSED Indicator 10 Manual Trip Button 11 Escutcheon Assembly 12 Manual Close Lever 13 Padlock Hasp 14 Motor Disconnect Switch 15 Automatic Trip Indicator 16 Removable Maintenance Handle 17 Position Indicator 18 Spring Charging Motor 19 Positioning Pins 20 Side Latches 21 Racking Cam Assembly Figure 1 Typical Electrically Operated K Line Plus Circuit Breaker ...

Page 6: ... The racking shutter of all K Line Plus circuit breakers allows access to the racking shaft when lifted The circuit breaker must be tripped before the shutter can be lifted This prevents racking the circuit breaker with the main contacts closed The padlock hasp holds the racking shutter closed when the hasp is activated Instructions appear on the side of the front escutcheon of the circuit breaker...

Page 7: ...positions This switch is located in the lower left portion of the circuit breaker Optionally EO breakers and MO breakers with shunt trip can be fitted with a 16 pole switch which offers an additional four each a and b contacts for customer use Undervoltage Trip Device Optional The electrically reset undervoltage trip device UVD is a single phase device which automatically trips the circuit breaker...

Page 8: ...Optional Interconnected cradle mounted linkage permits only one of two horizontally or vertically adjacent circuit breakers to be closed at any time when in the CONNECTED position KIRK Key Interlock Optional Positions for mounting a KIRK Key interlock are available with accessibility through the closed compartment door The Kirk Key is released only when the linkage on the cradle locks the circuit ...

Page 9: ...result from failure to properly adjust the circuit breaker trip device To adjust the settings of the MPSC 2000 trip device see the instructions in IB 6 1 2 8 1A A trip operation indicator or target is provided on the face of the MPSC 2000 unit When the MPSC 2000 determines that a trip is necessary it will both signal the magnetic latch and display the trip target with an orange day glo color Since...

Page 10: ...rgized All tests of the circuit breaker should be done with the circuit breaker in the TEST position Installation To insert the circuit breaker into its mating cubicle proceed as described below 1 The circuit breaker contacts must be OPEN and the racking crank turned in the counterclockwise direction fully against its stop On electrically operated circuit breakers the motor disconnect switch shoul...

Page 11: ...C 1 51 2 a AS Trip Control Device 5 P18 A5 P4 P20 P8 2 P6 A2 P2 P19 P22 P1 P10 Solid State 3A 1 3 A3 P17 4 Trip A4 2 P5 4A 1 7 P9 P3 80 19 17 15 A14 A18 A16 23 21 A22 A20 14 18 16 20 22 A15 A21 A19 A17 A23 5 6 AS a 10 AS 9 a 12 AS 11 b 14 AS 13 a 16 AS 15 b 53 65 CSCS CSCS 64 63 56 57 NO C C NO B21 32 31 B22 B13 B9 B11 B7 34 32 36 B15 B17 B19 38 40 42 44 19 17 18 a AS 20 21 23 b AS 22 AS a 24 35 3...

Page 12: ...ot Used pin out assignments 6 The assignments for pins B3 B6 will differ depending on whether the DESP option has been supplied See the MPSC 2000 schematic supplied with the breaker Notes 1 These assignments are provided for reference only and may be changed due to special requirements Some pins or plugs may not be present on all breaker configurations See the breaker schematic wiring diagram s fo...

Page 13: ...ance handle hooked section in the long slot on the pawl carrier Refer to Figure 4 The small tab on the maintenance handle will fit the small hole of the pawl carrier Using a pumping motion rotate the pawl carrier until the ratchet wheel no longer rotates At this point the spring charged indicator will indicate SPRINGS CHARGED The circuit breaker can be closed manually with the manual close lever N...

Page 14: ...s necessary to charge the closing springs and or operate the circuit breaker during maintenance keep hands and tools away from operating parts Circuit breakers should be withdrawn to the TEST position for checking the breaker operation For further inspection adjustments cleaning or parts replacement the circuit breaker should be withdrawn and moved to a suitable work area Periodic Maintenance Insp...

Page 15: ...xcess soot from the arc chute and blow any excess away with clean dry compressed air Arc Chute Replacement 1 Properly position the arc chute in the upper molding 2 Position retainer and insert and tighten screw 3 Replace the MPSC 2000 trip device observing all recommendations and warnings above Contact Inspection 1 Discoloration signs of burning and pitting on the arcing contacts is normal unless ...

Page 16: ...ason for making any adjustment the locking hardware will become ineffective when adjustments are made at each maintenance period regardless of whether they are needed or not Operating experience indicates that the contact gap adjustment is the only one normally required during the periodic maintenance interval When contacts are replaced or abraded during cleaning contact gap adjustment is mandator...

Page 17: ... service operation with the charging cranks reset and the closing springs discharged CONTACT PRESSURE Refer to Figure 8 The main contact adjustment is to be made with the breaker in the latched closed position The self locking adjusting stud 1 is to be turned to provide contact pressure such that a 0 750 inch shim will just fit the space A at the rear of the moving main contacts 2 On 800A models w...

Page 18: ...ripping the circuit breaker 4 Back off the adjusting screw 3 approximately two full turns Tripper Bar Latch Engagement Refer to Figure 9 The tripper bar latch engagement adjusting screw 4 is located adjacent to the latch engagement adjusting screw 3 To adjust the tripper bar latch engagement proceed as follows 1 Back off the adjusting screw 4 to assure excessive tripper bar travel 2 Close the circ...

Page 19: ...ed voltage to terminals 3 and 5 of the circuit breaker secondary disconnects Magnetic Latch Device The magnetic latch device in K Line Plus breakers does not require adjustment PROCEDURE FOR FIELD TESTING THE MPSC 2000 SOLID STATE TRIP SYSTEM There are two ways to evaluate the MPSC 2000 solid state trip system primary current injection through the breaker main contacts and secondary current inject...

Page 20: ...7 The term Range Selection is used herein for consistency with previous MPS type devices and refers to the value of the Rating setting of the device Like the previous MPS type devices the MPSC 2000 is capable of operating at two basic ratings one equal to the maximum frame continuous current rating and one equal to one half the frame rating For example on an 800A breaker the MPSC 2000 rating can b...

Page 21: ...ompletely assembled circuit breaker and not on individual parts Temperature At Which Tests Are To Be Made Dielectric tests shall be made at any temperature between 10 C and 55 C Magnitudes And Points of Application Of Test Voltage The dielectric test shall be applied as follows 1 With circuit breaker in the open position apply 1 320 volts a Between live parts including both line and load terminals...

Page 22: ...B p n 712994 A00 Anderol synthetic lubricant is also available as a spray Anderol 732 Anderol 732 is useful as a solvent for removing old lubricant dirt and debris in the mechanism However it cannot be used as a substitute for Anderol 757 4 Apply DAG 154 Acheson Colloid Inc to the following parts in accordance with ABB Specification 51626 a The surface of the secondary close latch b The main shaft...

Page 23: ...IB 6 2 11 1 1C Page 23 ABB NOTES ...

Page 24: ...IB 6 2 11 1 1C Page 24 ABB NOTES ...

Page 25: ...IB 6 2 11 1 1C Page 25 ABB NOTES ...

Page 26: ...IB 6 2 11 1 1C Page 26 ABB ABB Inc P O Box 100524 Florence South Carolina 29501 Phone 843 413 4700 Fax 843 413 4850 ABB ...

Reviews: