4.2 Configuring the PROFINET network settings
General
The following procedure describes how to change the PROFINET network settings
using RobotStudio.
External tools
These settings, except
Connection
, can also be configured using an external
PROFINET network browser tool.
Many external PROFINET tools have overlapping functionality when it comes to
changing the network settings. This means that for example a network address
set in RobotStudio can be overwritten by an external tool in a subsequent step.
The overwritten settings will not be applied immediately but after the next restart
of the IRC5 controller. Therefore, it is important to have a good working procedure
to avoid that parameters are overwritten.
Note
Note that the network settings are set for the
Connection
, i.e. the physical
connector on the main computer used for the PROFINET network.
This means that the network settings are shared between the internal device and
the internal controller if the IRC5 controller acts as both on the PROFINET
network.
Network configuration
Use this procedure to configure the PROFINET network settings in the IRC5
controller, using RobotStudio.
Note
Action
Start RobotStudio and connect to the
IRC5 controller. Request write access.
1
For more information about the paramet-
ers, see
.
Open the
Configuration Editor
and select
I/O System
.
2
xx1400002055
In the
Type
list click
Industrial Network
and edit the parameter
PROFINET
.
Edit the parameter values, if applicable.
•
Connection
, the physical connect-
or on the main computer.
•
Configuration File
, empty for intern-
al device.
•
PROFINET Station Name
, user
defined.
•
Simulated
, user defined.
Click
OK
.
3
Configuring the internal device on page 38
Restart the controller, or continue with the
next step of the configuration.
4
Continues on next page
36
Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
4 Configuring the internal device and external controller
4.2 Configuring the PROFINET network settings
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Application manual PROFINET Controller Device...
Page 28: ...This page is intentionally left blank...
Page 34: ...This page is intentionally left blank...
Page 40: ...This page is intentionally left blank...
Page 48: ...This page is intentionally left blank...
Page 74: ...This page is intentionally left blank...
Page 78: ...This page is intentionally left blank...
Page 86: ......
Page 87: ......