Step 4A Single Phase
-
Connect 120/240 Single Phase AC Input Section
Sizing external protectors and wire for all rectifier positions (3 or 6) provides full power for all rectifier positions.
Recommended External Protection and Minimum Wire Size
-
6 AWG max.
19” 3
rectifier configuration
120V~ Phase to Neutral
(1200W per rectifier
max)
240V~ Phase to Neutral
(2725W per rectifier max)
Single
-
Phase Rectifiers
Rectifier Positions Powered
Maximum
Rectifiers
per Feed
External
Feed
Protector
Minimum
Wire
External
Feed
Protector
Minimum
Wire
1
1
20A
14AWG
20A
14AWG
2
2
40A
8AWG
40A
8AWG
3
3
60A
6AWG
60A
6AWG
Recommended External Protection and Minimum Wire Size
-
6 AWG max.
23” 6
rectifier configuration
120V~ Phase to Neutral
(1200W per rectifier
max)
240V~ Phase to Neutral
(2725W per rectifier max)
Single
-
Phase Rectifiers
Rectifier Positions Powered
Maximum
Rectifiers
per Feed
External
Feed
Protector
Minimum
Wire
External
Feed
Protector
Minimum
Wire
1
1
20A
14AWG
20A
14AWG
2
2
40A
8AWG
40A
8AWG
3
3
60A
6AWG
60A
6AWG
4
4
80A
4AWG
80A
4AWG
5
5
100A
2AWG
100A
2AWG
6
6
120A
1AWG
120A
1AWG