QUICK START GUIDE

 

Infinity B (NE

-

B) G240 System 

-

48V, +24V, 

+24V/

-

48V or –

48

V/+24V

 

• 

 

 

 

Use  a  #10  or 

1/4” 

diameter  double

-

hole  lug  on 

5/8” 

center (Not provided) to ground the chassis; Torque 

connections to 35 in

-

 lbs using 

5/16” 

nut driver

 

Shelf Chassis 
Ground Options

 

The  ac  input  panel  is  directly  above  the  top  row  of 

power modules. 

1” 

and 

1

-

1/2” 

conduit knockouts are 

located  on  the  left  and  right  ends  of  the  ac  panel. 

Each  rectifier  position  is  factory  configured  for 

individual  208/220VAC  inputs.  Individual  inputs 

require  20A  protectors  and  10  AWG  wires.  Two 

rectifier positions can be fed from one ac source by 

installing  the  provided  jumpers.  When  using  one 

input  for  two  rectifiers  a  40A  protector  and  8  AWG 

wire  is  required.  Recommend  two 

1

-

1/2” 

conduits 

feeding up to 8 rectifiers per conduit; (16) 10 AWG 

 

Rectifiers

 

Rectifiers

 

Rectifiers

 

Rectifiers

 

41

 

42

 

31

 

32

 

21

 

22

 

11

 

12

 

13

 

14

 

23

 

24

 

33

 

34

 

43

 

44

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L1

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

L2

 

Summary of Contents for Infinity B G240 System +24V/-48V

Page 1: ...ectifiers 41 42 31 32 21 22 11 12 13 14 23 24 33 34 43 44 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 0 JJll111111111111111 aii11111m1111i1i tllllllllllllllllll n1111m1111if11 lllllllllllllllllb of 11 1IIIIIIIIIIIIIIUU J IIIIIIIIIIIIIIIUlb u11111m111iiiw 11111111111111111111 nfif11 um11111111 1ll111111lllllllllb m11111m111mr i iHHlllllllllllllb i...

Page 2: ...tach the individual 10 AWG AC input wires for each position and torque the wire clamps to 10 inch lbs 2 For applications using one ac feed for every two rectifiers Use a pair of needle nose pliers to remove the divider between the individual rectifier wire clamps that will share the ac input 3 Install a strap between the two terminal blocks Secure the strap in posi tion with two screws and torque ...

Page 3: ...Set Jumper 11 to for 24Vdc systems or for 48V 24V Factory Default systems 2 Set jumpers 1 thru 10 for the ten alarm relays as Close or Open on alarm Factory default setting is Close on alarm The Alarm relay jumpers are located under the sliding cover on top of the controller see figure below Note The optional Millennium II rack mount controller can be used instead of the Pulsar when additional con...

Page 4: ...nt O BK Fuse Alarm Major 24V Open Battery String Fuse Alarm Major 48V Standard Controller Alarm Output Defaults Pin Color Option 1 Color Option 2 PCR Power Critical BL BL PCR_C Power Critical_C 11 BL BK PMJ Power Major PMJ_C Power Major_C 12 O BK PMN Power Minor PMN_C Power Minor_C 13 G BK R1 Battery On Discharge BR R1_C Battery On Discharge_C BD_C 14 W BK R2 Very Low Voltage VLV BK R2_C Very Low ...

Page 5: ... rectifiers and converters The outputs are located on the rear of the shelf The shelf is designed to distribute bulk power only there are no DC output protectors in the shelf Lug landings accommodate 3 8 di ameter lugs on 1 centers spaced 1 75 apart Three 750 MCM Flex lugs can be connected per bus Bus extensions are provided to land four additional cables back to back Standard Controller Alarm Pin...

Page 6: ...ype the default IP address in the web browser address field Server mode is a temporary setting once configuration is complete reset the controller to Client or Static before connecting to the network Static is the factory default setting and the typical setting for most networks Warning Do not connect J5 LAN port to a network when set to Server Controller Alarm Status The display changes colors Gr...

Page 7: ... 58 50 58 50 High Float Voltage Major Alarm 50 to 60V 57 00 57 00 57 00 High Float Voltage Minor Alarm 50 to 60V 56 00 56 00 56 00 Rectifier System Float Voltage 42 to 56 5V 54 48 52 08 54 40 Battery on Discharge Float Alarm 46 to 55V 51 00 50 00 51 00 Very Low Float Voltage Alarm 40 to 51V 46 00 46 00 46 00 Rectifier On Threshold 40 to 51V 44 00 44 00 44 00 Front Display Menu Map ...

Page 8: ...ccomplished with a Daisy Chained series of QS873 probes connected to J2 The Probes are used to monitor battery temperature and mid string voltage ES771 required to monitor voltage Bolt the Probe under the terminal connector hardware NOT under the connecting lug Temperature monitoring Temperature and voltage monitoring ...

Page 9: ...eed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB...

Reviews: