background image

9

1MRK 500 080-UEN rev. -

Setting of IED 670 functions

The Parameter Setting tool is accessible in another part of the PCM 600 struc-
ture, open it by right clicking on the IED and select the setting tool. The Param-
eter setting tool will show the functions configured and compiled in the 
CAP 531 tool. Navigate through the functions menu and set the General set-
tings and those for the setting groups utilized. Note that the number of the set-
ting group used is settable on the number of setting groups function block. This 
avoids switching to a setting group with default setting values that is not used. 
The changed parameters will be in bold text. Copy and paste are supported for 
your convenience.

Changed General setting parameters require a full restart of the IED and are not 
generally changed once a plant has been commissioned. Setting group changes 
take place immediately. There are Normal user and Advanced user settings. 
Advanced user settings are seldom changed settings such as user defined setting 
characteristics, function times and settings. You can simply toggle between the 
two on the tool menu bar if something needs to be checked. Download the set-
tings to the IED by clicking the download symbol on the menu. Individual 
parameters, the complete IED structure, General settings and Setting groups 
can be downloaded individually or according to preferences. It is advisable to 
download individual functions and read back the values for verification.

Disturbance recorder handling

The IED 670 includes a Disturbance recorder (DR) with 40 analog and 96 digi-
tal channels. It has a default configuration and signals have been given names 
which will show-up on the records. The binary (and also analog) signals can, by 
setting, be made visible or hidden and to trigger a disturbance recording. Select 
according to your preference for each of the 96 binary signals. If you need to 
connect other signals or more signals (or change names) you need to use the 
CAP 531 application configuration tool. Disturbance records are stored in 
COMTRADE format which can be used for evaluation with most tools.

Disturbance records are uploaded from the PCM 600 toolbox with a scheduler 
or manually. Open the Disturbance recorder tool. Right click on the lower part 
where the IED disturbances are shown and upload the list. Mark the distur-
bances you want to move to the PC and upload, you will find this option by 
right clicking the mouse.

Uploaded disturbances, refreshed if required, can be shown either in a report 
using the default template or other templates created with the available wizard. 
The short report will be in pdf format and can be arranged to be automatically 
e-mailed, to defined adresses. There is also an option that shows the disturbance 
in a viewer such as WinEve. Select this option by right clicking on the selected 
disturbance and evaluate in detail the cause of the recorded disturbance.

Figure 10: Disturbance handler

Note! 

In a commissioned plant it is not permitted to 
change settings to values other than those in 
another pre-tested setting group. The Block-
Set function block shall be activated after 
commissioning to prevent any change of Set-
tings, Configuration, Signal matrix or graphi-
cal HMI.

Note! 

IED 670 is set in primary values for all func-
tions!

Summary of Contents for IED 670

Page 1: ...atus bars ordering No 1MRK 000 020 BT are required A suitable test switch with contacts for example for a line protection IED such as REL 670 is selectable when ordering This allows commissioning and maintenance testing of the complete IED with many functions from one test handle Note The use of test switch RTXP24 NO contact 29 30 to perform software blocking has several advantages and is used dur...

Page 2: ...n terminal or port on the rear side of the IED is numbered The numbers are stamped into the rear panel above each opening Viewed from the rear the lowest numbers are to the left and increase to the right All numbers begin with an X followed by two or three digits Analog inputs can be ordered with ring lug connectors as an alternative The analog inputs are dimensioned for conductor cross section ar...

Page 3: ... used to navigate between different screens and data To change a setting select an item in the menu structure and change it using the up and down keys on the HMI After selecting parameter values move up through the menu system by repeatedly pushing the left arrow key until a dialog box appears where changes can be confirmed or cancelled The LEDs on the front panel of the IED are configured with th...

Page 4: ...n PCM 600 The user can only LogOn or LogOff on the LHMI of the IED there are no users groups or functionalities that can be defined on the IED LHMI The display time out is set to 60 minutes at delivery At delivery the default user is the SuperUser No LogOn is required to operate the IED until a user has been created with the UMT See Application manual for more details The Help screen The help scre...

Page 5: ... LANTIME which has been verified for Network Time Protocol NTP format The clock is connected to the station bus communication switch Other clocks can also be used but please check back if they were verified by ABB the same GPS satellite clock can synchronize an IED via a binay input B I with the disadvan tage of using copper cables over the whole substation The IED can also be synchronized from an...

Page 6: ... Connectivity Packages for PCM 600 Prerequisites To operate with PCM 600 there must be at least one communication Con nectivity Package and one IED Connectivity Package installed and selected to be used with PCM 600 The IED Connectivity Packages are delivered with the IED s Start the PCM 600 from the desktop and build a new project For the new project your system structure with stations voltage le...

Page 7: ...ts or outputs and type v to give variable names to a connection Connect to the other end with the same signal name alternatively draw the con nection with the connector tool Outputs may go to several function blocks but inputs may only be connected to one so an OR gate might be required Signals to other sheets shall preferably be drawn to the edge of the sheet where there is a red line This ensure...

Page 8: ... appropriately chosen default IO arrangement but the tripping signals are connected to the physical IO supplied as basic supply Alarm signals and the like must be configured per application Analog signals can be connected to separate CT cores VT fuses and so on but different protection functions may also be connected to the same analog chan nels according to user preferences and the availability o...

Page 9: ...order DR with 40 analog and 96 digi tal channels It has a default configuration and signals have been given names which will show up on the records The binary and also analog signals can by setting be made visible or hidden and to trigger a disturbance recording Select according to your preference for each of the 96 binary signals If you need to connect other signals or more signals or change name...

Page 10: ...s document Each protection function has a function block with both analog and binary inputs and outputs The function blocks are described in detail in the Technical reference manual The analog inputs are connected by default to a pre process ing analog block in the configuration and a cross reference table is generated in the parameter setting tool PST which is part of the PCM 600 Ensure that the ...

Page 11: ...y the IED This can be caused by a lost connection a clock failure or delayed signals caused by software handling In the latter case the signal will normally disappear automat ically Application problems The function does not trip or show up on the HMI Note First check that the function is set to ON and that it is not blocked or in test mode Verify the measurement by checking Test Function status I...

Page 12: ...MRK 505 278 UEN Buyer s guide 1MRK 506 279 BEN Documents related to REC 670 Identity number Operator s manual 1MRK 511 188 UEN Installation and commissioning manual 1MRK 511 189 UEN Technical reference manual 1MRK 511 187 UEN Application manual 1MRK 511 190 UEN Buyer s guide 1MRK 511 191 BEN Documents related to RET 670 Identity number Operator s manual 1MRK 504 087 UEN Installation and commission...

Reviews: