1MRK 500 080-UEN rev. -

Configuring the IED 670 functions

Start-up

The PCM 600 toolbox is used to configure protection IEDs in the IED 670 
series. The tool includes a project manager and tools for all necessary tasks. 
Install the PCM 600 in your computer first and then install the IED connectivity 
packages. Start the PCM 600 and build a new project.

System requirements:

Operating system: Windows 2000 SP4 / XP SP2

Hardware requirements, minimum/recommended:

Physical RAM memory: 512 MB / 1 GB

Free hard disk space: 500 MB / 1 GB

Processor: Pentium 900 MHz / Pentium 2 GHz

To start installation of PCM 600 insert the installation CD into the CD-drive. If 
installation doesn’t start automatically, execute setup.exe in the root folder on 
the installation CD. When the installation begins select the software that you 
prefer to install and follow the instructions to complete the installation.

Note! If you don’t have Microsoft SQL Server Desktop Engine already installed 
this will be installed when installing PCM 600. Installation of PCM 600 can 
only be made as a standalone installation.

After the installation has completed, start Connectivity Package Manager from 
desktop to activate installed Connectivity Packages for PCM 600.

Prerequisites:

To operate with PCM 600, there must be at least one communication Con-
nectivity Package and one IED Connectivity Package installed and selected 
to be used with PCM 600. The IED Connectivity Packages are delivered with 
the IED’s.

Start the PCM 600 from the desktop and build a new project. For the new 
project your system structure with stations, voltage levels, bays and IEDs is 
built-up in the plant structure. Right click your mouse or locate the plant struc-
ture components in the menu.

Setting up your communication

To communicate with the IED the following set-up is required under the com-
munication structure and/or properties for an IED.

The TCP/IP address on the PC must be set. If your computer setting is DHCP the 
connection will not work. Set-up your PC manually with values close to the values 
set in the HMI tree, under General settings/Communication/Network Interface/
Ethernet. Note! You need to have administrator rights to start up the communica-
tion.

The IP address is set under communication structure (right click the plant structure 
tab) Select the IED and set the IP address under properties as shown in figure 6.

Set the SPA address for the IED under the communication structure. Open the IED 
and the LDO and set the address to 30. See figure 8.

Figure 6: Setting IP.

Figure 7:  OPC Server configuration.

Figure 8:  SPA Address.

Summary of Contents for IED 670

Page 1: ...atus bars ordering No 1MRK 000 020 BT are required A suitable test switch with contacts for example for a line protection IED such as REL 670 is selectable when ordering This allows commissioning and maintenance testing of the complete IED with many functions from one test handle Note The use of test switch RTXP24 NO contact 29 30 to perform software blocking has several advantages and is used dur...

Page 2: ...n terminal or port on the rear side of the IED is numbered The numbers are stamped into the rear panel above each opening Viewed from the rear the lowest numbers are to the left and increase to the right All numbers begin with an X followed by two or three digits Analog inputs can be ordered with ring lug connectors as an alternative The analog inputs are dimensioned for conductor cross section ar...

Page 3: ... used to navigate between different screens and data To change a setting select an item in the menu structure and change it using the up and down keys on the HMI After selecting parameter values move up through the menu system by repeatedly pushing the left arrow key until a dialog box appears where changes can be confirmed or cancelled The LEDs on the front panel of the IED are configured with th...

Page 4: ...n PCM 600 The user can only LogOn or LogOff on the LHMI of the IED there are no users groups or functionalities that can be defined on the IED LHMI The display time out is set to 60 minutes at delivery At delivery the default user is the SuperUser No LogOn is required to operate the IED until a user has been created with the UMT See Application manual for more details The Help screen The help scre...

Page 5: ... LANTIME which has been verified for Network Time Protocol NTP format The clock is connected to the station bus communication switch Other clocks can also be used but please check back if they were verified by ABB the same GPS satellite clock can synchronize an IED via a binay input B I with the disadvan tage of using copper cables over the whole substation The IED can also be synchronized from an...

Page 6: ... Connectivity Packages for PCM 600 Prerequisites To operate with PCM 600 there must be at least one communication Con nectivity Package and one IED Connectivity Package installed and selected to be used with PCM 600 The IED Connectivity Packages are delivered with the IED s Start the PCM 600 from the desktop and build a new project For the new project your system structure with stations voltage le...

Page 7: ...ts or outputs and type v to give variable names to a connection Connect to the other end with the same signal name alternatively draw the con nection with the connector tool Outputs may go to several function blocks but inputs may only be connected to one so an OR gate might be required Signals to other sheets shall preferably be drawn to the edge of the sheet where there is a red line This ensure...

Page 8: ... appropriately chosen default IO arrangement but the tripping signals are connected to the physical IO supplied as basic supply Alarm signals and the like must be configured per application Analog signals can be connected to separate CT cores VT fuses and so on but different protection functions may also be connected to the same analog chan nels according to user preferences and the availability o...

Page 9: ...order DR with 40 analog and 96 digi tal channels It has a default configuration and signals have been given names which will show up on the records The binary and also analog signals can by setting be made visible or hidden and to trigger a disturbance recording Select according to your preference for each of the 96 binary signals If you need to connect other signals or more signals or change name...

Page 10: ...s document Each protection function has a function block with both analog and binary inputs and outputs The function blocks are described in detail in the Technical reference manual The analog inputs are connected by default to a pre process ing analog block in the configuration and a cross reference table is generated in the parameter setting tool PST which is part of the PCM 600 Ensure that the ...

Page 11: ...y the IED This can be caused by a lost connection a clock failure or delayed signals caused by software handling In the latter case the signal will normally disappear automat ically Application problems The function does not trip or show up on the HMI Note First check that the function is set to ON and that it is not blocked or in test mode Verify the measurement by checking Test Function status I...

Page 12: ...MRK 505 278 UEN Buyer s guide 1MRK 506 279 BEN Documents related to REC 670 Identity number Operator s manual 1MRK 511 188 UEN Installation and commissioning manual 1MRK 511 189 UEN Technical reference manual 1MRK 511 187 UEN Application manual 1MRK 511 190 UEN Buyer s guide 1MRK 511 191 BEN Documents related to RET 670 Identity number Operator s manual 1MRK 504 087 UEN Installation and commission...

Reviews: