![ABB IEC 61850 Edition 2 Communication Protocol Manual Download Page 53](http://html.mh-extra.com/html/abb/iec-61850-edition-2/iec-61850-edition-2_communication-protocol-manual_2732053.webp)
7.2
IEC 61850 data model description Edition 2
GUID-B7C6120F-3A98-4DD4-8B4B-CCD2EEC9EE29 v3
The IEC 61850 data model description Edition 2 is delivered in online help format
on the IED Connectivity package USB flash drive as part of the product delivery.
The latest versions can be downloaded from
www.abb.com/protection-control
7.2.1
Using the online help file
GUID-0436EB93-842F-4908-85CB-93BCFED7AC93 v5
1.
Download the online help file from the link below and save the file to your
local hard drive.
•
) for IEC 61850 data model description, Edition
2, 670 series 2.2
•
) for IEC 61850 data model description, Edition
2, RER670 2.2
2.
Double-click the file.
3.
Clear the
Always ask before opening this file
check box.
4.
Click
Open
.
7.2.2
DO presence condition description
GUID-63E36A26-DCFF-49CD-9C58-CE783031532C v2
Table 2:
Conditions used by the Logical Node description
Condition
Description
AtLeastOne
At least one of marked elements shall be present.
M
Element is mandatory.
MFcond
Not yet defined.
Mmulti
At least one element shall be present; all instances have an instance number
within range [1, 99] (see Part 7-1).
MOrootLD
Element is mandatory in the context of a root logical device; otherwise it is
optional.
O
Element is optional.
Omulti
Zero or more elements may be present; all instances have an instance number
within range [1, 99] (see Part 7-1).
1MRK 511 393-UEN A
Section 7
Logical node data model
670 series 2.2 IEC
47
Communication protocol manual