IEC08000178.vsd
IED Name
AccessPoint
Address
GSE
IED Name
AccessPoint
Address
GSE
Services
Authentication
LDevice
DAI
DOType
DAType
EnumType
Substation
VoltageLevel
Bay
LNode
IED
LD
LN
IED
LD
LN
Communucation
Subnetwork
Connected AP
IED
AccessPoint
Server
GOOSE Control
LN0
LN
DataSet
DOI
DataTypeTemplates
Report Control
Inputs
DOI
SettingControl
LNodeType
DOType
DAType
EnumType
DO
DA
IE
D
SDO
BDA
S
ta
ti
on
C
om
m
un
IEC08000178 V1 EN-US
Figure 2:
IEC 61850: Principle structure of the SCL XML file
The arrows show the link between the different sections given when an IED is
integrated in the substation structure and/or in the communication structure. All
needed logical nodes of an IED are linked to the substation section by the SCL
tool.
A reference to GOOSE Control Blocks (GoCB) is included in the communication
section when GoCB is configured.
3.1
The substation section
SEMOD129763-4 v4
The substation description in IEC 61850-6 clause 9 describes the arrangement of
the primary equipment. In addition, it also includes a list of the applied logical
nodes and the relation of those logical nodes to the primary equipment.
Section 3
1MRK 511 393-UEN A
Substation Configuration description Language (SCL)
24
670 series 2.2 IEC
Communication protocol manual