![ABB IEC 61850 Edition 2 Communication Protocol Manual Download Page 36](http://html.mh-extra.com/html/abb/iec-61850-edition-2/iec-61850-edition-2_communication-protocol-manual_2732036.webp)
Import the SCD file to PCM600 to receive GOOSE data. For each IED that shall
receive GOOSE information, the received data is connected to the applications
using SMT in PCM600. To be able to import scd-file to PCM600, 61850
engineering mode in PCM must be disabled.
3.5
Engineering concept in IEC 61850-6
GUID-FFE87459-FBC1-4D85-A6B3-7BD6F576ECE4 v3
•
Top-down approach means that the system engineering tool has ICD files
available for each IED to be included in the system configuration. The ICD
files may be of the template type and represent a pre-configured IED.
•
Bottom-up approach means that the configurations are produced by the IED
tool, and that are exported as CID, or IID files (or SCD file) to be imported
into the system tools.
…
IED A
IED B
IED Z
Client A
IED
tool
System
tool
IEC09000151-2-en.vsd
Client B
IEC09000151 V2 EN-US
Figure 5:
Relation between system and IED tools
Regardless of the engineering approach, the idea is that the IED tool provides the
CID, ICD, or IID file for each IED. These ICD/CID/IID files are then imported
into the system tool and merged into a SCD file, representing the complete
substation or a part of the substation, like one for each voltage level.
Section 3
1MRK 511 393-UEN A
Substation Configuration description Language (SCL)
30
670 series 2.2 IEC
Communication protocol manual