Commissioning
96 2CDC 505 056 D0208 | SA/S
Value
Bit 1
Bit 0
State
Description
0
0
0
Enabled
If the communication object
Forced operation
receives a telegram with
the value 0 (binary 00) or 1 (binary 01), the output is enabled and can be
actuated via different communication objects.
1
0
1
Enabled
2
1
0
Forced
OFF
If the communication object
Forced operation
receives a telegram with
the value 2 (binary 10), the output of the Switch Actuator is switched off
and remains disabled until forced operation is switched off again.
Actuation via another communication object is not possible as long as
forced operation is activated.
The state of the output at the end of forced operation can be
parameterized.
3
1
1
Forced ON
If the communication object
Forced operation
receives a telegram with
the value 3 (binary 11), the output of the Switch Actuator is switched on
and remains disabled until forced operation is switched off again.
Actuation via another communication object is not possible as long as
forced operation is activated.
The state of the output at the end of forced operation can be
parameterized.
Object value "Forced positioning"
on bus voltage recovery
This parameter is only visible if forced operation is activated.
Depending on whether the forced operation object is a 1 bit or 2 bit communication object, there are
two different parameterization possibilities available:
1 bit communication object:
Options:
inactive
active
•
inactive
: Forced operation is switched off, and the output behaves in the same way as with
parameter
Reaction when forced operation and all safety Priority x end
.
•
active
: Forced operation is active again after bus voltage recovery. The contact position of the
output is determined by the parameterization of
Contact position if forced operation
.