ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 125
Enable function "valve purge"
Options:
no
yes
Cyclic valve purge prevents deposits from forming in the valves.
•
no
: Parameter window A:
Valve Purge
is not enabled for output A.
•
yes
: Parameter window A:
Valve Purge
and communication objects
Trigger valve purge
and
Status
valve purge
are enabled for output A.
Enable function "current detection"
Options:
no
yes
•
no
: Parameter window A:
Current Detection
is not enabled for output A.
•
yes
: Parameter window A:
Current detection,
and communication object
Contact monitoring
,
are enabled for output A.
Please note
These parameters and their functions are only visible for Switch Actuators with current detection. The
actuators with integrated current detection are recognizable by a number 6 as the third number of the
type designation, e.g. SA/S 2.16.