Commissioning
© 2006 ABB STOTZ-KONTAKT GmbH
18
ABB i-bus
®
EIB / KNX
Cyclic switch position recall (only if cyclic recall greater than 0)
Options:
no/yes
Option
no
= do not recall switch position
Option
yes
= recall switch position
With this parameter recall of the switch position is activated.
Note:
The cycle time for this purpose is set in the parameter
Switch
positions cyclic recall every [0…255 hours, 0 = deactivated]
in the parameter window “General”.
If the switch positions are recalled cyclically, ensure that on the
recalling device, e.g. a switch actuator channel, the R flag is set
in the communication object to be recalled. Otherwise the Data
Logging Unit can not recall the switch position.