FEP630, FEH630
ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
13
4
Transport and storage
Inspection
Check the devices immediately after unpacking for possible
damage that may have occurred from improper transport.
Details of any damage that has occurred in transit must be
recorded on the transport documents.
All claims for damages must be submitted to the shipper
without delay and before installation.
Transport
DANGER
Life-threatening danger due to suspended loads.
In the case of suspended loads, a danger of the load falling
exists.
• Standing under suspended loads is prohibited.
WARNING
Risk of injury due to device slipping.
The device's center of gravity may be higher than the harness
suspension points.
• Make sure that the device does not slip or turn during
transport.
• Support the device laterally during transport.
NOTICE
Potential damage to the device!
The protection plates or protection caps mounted at the
process connections on devices with PTFE / PFA liners may
only be removed immediately before installation.
• To prevent possible leakage, make sure that the liner on
the flange is not cut or damaged.
G12034
Figure 7: Transport instructions -
≤
DN 450
Flange devices
≤
DN 450
• Use carrying straps to transport flange designs smaller than
DN 450.
• Wrap the carrying straps around both process connections
when lifting the device.
• Chains should not be used, since these may damage the
housing.
Flange devices > DN 450
G10645
Figure 8: Transport instructions - > DN 450
• Using a forklift to transport flange device can dent the
housing.
• Flange devices must not be lifted by the center of the
housing when using a forklift for transport.
• Flange devices must not be lifted by the terminal box or by
the center of the housing.
• Only the transport lugs fitted to the device can be used to lift
the device and insert it into the piping.