7.6.2 Maximum dimensions of the connections
For fixed version HD4/R circuit-breakers, the connections must
be shaped and installed in accordance with the indications
given in the overall dimensions and in compliance with the dis-
tances indicated.
7.6.3 Surface treatment of the connections
The connections can be made of bare copper or bare alumin-
ium. However, it is always advisable to silver-plate the contact
surfaces.
The thickness of the surface treatment must be even and regu-
lar.
7.6.4 Assembly of the connections
– Make sure that the contact surfaces of the connections are
perfectly flat and without burrs, traces of oxidation or de-
formities caused by drilling or impact sustained.
– Depending on the conductive material used and the surface
treatment given, the operations indicated in the following
table must be carried out on the surface contact of the con-
ductor.
Bare copper
Clean with a fine file or emery cloth
Smear 5RX Moly
Copper or silver-
plated aluminium
Clean with a rough dry cloth
Only if there are traces of oxidation that are difficult
to shift, clean with ultra-fine grain emergy cloth and
take care not to remove the surface layer
Repeat the surface treatment if necessary
Bare aluminium
Clean with a metal brush or emery cloth
Immediately smear neutral grease over the contact
surfaces
Insert a bi-metal copper-aluminium strip with
beaded surfaces between the aluminium
connection and the copper terminal (copper side
touching the terminal, aluminium side touching the
connection)
Assembly procedures
– Place the connections in contact with the circuit-breaker
terminals.
– Insert a spring washer and a flat washer between the head
of the bolt and the connection.
– The diameter of the flat washers must be able to distribute
the torquing pressure over a wide area.
– Tighten the bolt, taking care to prevent the insulating parts
from being stressed (consult the table with the rightening
torque values).
– Make sure that the connections do not exert any force on
the terminals.
– Carefully comply with the manufacturer’s instructions for
terminating the cables in cable connections.
Table of tightening torque values
Screw
Tightening torque values
M6
10 Nm
M8
30 Nm
M10
40 Nm
M12
70 Nm
7.7 Earthing
– Earth fixed version circuit-breakers by means of the spe-
cial screw marked with the relative symbol. Clean and de-
grease the area around the screw corresponding to a diam-
eter of about 30 mm. Use a conductor (busbar or cord) with
a cross-section conforming to the Standards in force.
– When the assembly is completed, cover the joint with vase-
line grease.
7.8 Connection of the auxiliary circuits
The minimum cross-section of the wires used for the auxiliary
circuits must not be less than the one used for the internal
cabling.
They must also be insulated for 3 kV test voltage.
7.8.1 Fixed version circuit-breakers
The auxiliary circuits of the circuit-breaker must be connected
by means of the terminal box installed in the circuit-breaker’s
operating mechanism.
The wires outside the circuit-breaker must be routed inside ap-
propriately earthed metal tubes or ducts.
Figure 8
Make sure that the circuit-breaker is open
and the closing springs discharged before
removing the operating mechanism cover to
access the terminal box.
7.8.2 Plug-in circuit-breaker
The auxiliary circuits of the plug-in or removable circuit-breaker
are fully wired in the factory through to the connector. Please
refer to the wiring diagram of the switchgear for the connec-
tions.
Summary of Contents for HD4/R
Page 2: ......
Page 21: ...21 7 9 Overall dimensions 7 9 1 Fixed HD4 R 12 24 kV 630 1250 A TN 7237 Figure 9 ...
Page 22: ...22 7 9 2 Fixed HD4 R 12 24 kV 630 1250 A TN 7234 Figure 10 ...
Page 24: ...24 7 9 4 Plug in HD4 S 12 24 kV 630 1250 A TN 7236 Figure 12 ...
Page 25: ...25 7 9 5 HD4 Uniair 12 24 kV 630 1250 A TN 7235 Figure 13 ...
Page 26: ...26 7 9 6 HD4 Uniair F 12 24 kV 630 A TN 7275 Figure 14 ...
Page 27: ...27 7 9 7 HD4 Uniair 2R 12 24 kV 630 1250 A TN 7274 Figure 15 ...
Page 28: ...28 7 9 8 HD4 Uniair A 12 24 kV 630 1250 A TN 7273 Figure 16 ...
Page 29: ...29 7 9 9 HD4 UniMix F 12 24 kV 630 1250 A TN 7366 Figure 17 ...
Page 30: ...30 7 9 10 HD4 R SEC 12 24 kV 630 800 A 1VCD003536 Figure 18 ...
Page 37: ......