5.7 Circuit-breaker specifications
5.7.1 General specifications of fixed circuit-breakers
with rh lateral operating mechanisms (12 - 17.5 - 24 -36 kV)
Circuit-breaker
HD4/R 12
HD4/R 17
HD4/R 24
HD4/R 36
Standards
IEC 62271-100
•
•
•
•
CEI EN 62271-100
(dossier 7642)
•
•
•
•
Rated voltage
Ur [kV]
12
17.5
24
36
Rated insulation voltage
Us [kV]
12
17.5
24
36
Withstand voltage at 50 Hz
Ud (1 min) [kV]
28
38
50
70
Impulse withstand voltage
Up [kV]
75
95
125
170
Rated frequency
fr [Hz]
50-60
50-60
50-60
50-60
Rated thermal current (40°C)
Ir [A] 630
800 1250 630
800 1250 630
800 1250 630
800 1250
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Isc [kA] 12.5
–
–
12.5
–
–
12.5
–
–
12.5 12.5 12.5
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
–
–
–
25
25
25
–
–
25
–
–
–
–
–
–
Short-time withstand current (3 s)
Ik [kA] 12.5
–
–
12.5
–
–
12.5
–
–
12.5 12.5 12.5
16
16
16
16
16
16
16
16
16
16
16
16
20
(6)
20
20
20
(6)
20
20
20
(6)
20
20
–
–
–
25
25
25
–
–
25
–
–
–
–
–
–
Making capacity
Ip [kA] 31.5
–
–
31.5
–
–
31.5
–
–
31.5 31.5 31.5
40
40
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
–
–
–
63
63
63
–
–
63
–
–
–
–
–
–
Sequence of operations
[O - 0.3s - CO - 15s - CO]
•
•
•
•
Opening time
[ms]
45
45
45
45
Arcing time
[ms]
10...15
10...15
10...15
10...15
Total break-time
[ms]
55…60
55…60
55…60
55…60
Closing time
[ms]
80
80
80
80
Overall dimensions
(maximum)
H [mm]
764.5
764.5
764.5
810
L [mm]
321
321
321
409
D [mm]
1049
(1)
/ 1189
(2)
1049
(1)
/ 1189
(2)
1049
(1)
/ 1189
(2)
1348
Pole center-distance [mm]
230 / 300
230 / 300
230 / 300
350
Weight
(3)
[kg]
103
(1)
- 105
(2)
103
(1)
- 105
(2)
103
(1)
- 105
(2)
110
Absolute gas pressure (nominal duty value)
[kPa]
380
380
380
380
Application of PR521 protection device
In [A] 40-80-250-1250
(4)
40-80-250-1250
(4)
40-80-250-1250
(4)
–
Application of REF 601 protection device
•
(5)
•
(5)
•
(5)
–
Standardized dimensions table
TN 7237
(1)
TN 7237
(1)
TN 7237
(1)
TN 7238
TN 7234
(2)
TN 7234
(2)
TN 7234
(2)
Wiring diagram
without protection
device installed
1VCD400017
1VCD400017
1VCD400017
1VCD400017
with PR521
1VCD400017
1VCD400017
1VCD400017
–
with REF 601
1VCD400114
1VCD400114
1VCD400114
–
Operating temperature
[°C]
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
Tropicalization
IEC: 60068-2-30, 60721-2-1
•
•
•
•
Electromagnetic compatibility
IEC 62271-1
•
•
•
•
(1)
230 mm pole center-distance
(2)
300 mm pole center-distance
(3)
increase the indicated weight by 20 kg for circuit-breakers with PR521 / REF 601 devices and 3 current sensors (15 kg only with 2 current sensors)
(4)
rated current of the current sensors (the PR521 device and the current sensors are available on request); at 24 kV, only 2 current sensors for PR521 (installed on the circuit-breaker’s
lateral poles) can be used with 230 mm center-distance between poles
(5)
the REF 601 device and the current sensors are available on request. The rated current of the REF 601 must be set in the relay and must be compatible with the rated current of the
circuit-breaker. The rated current that can be set with CEI 0-16 is 80 A or 250 A. With the CEI 0-16 version of REF 601, the circuit-breaker is always supplied with 3 phase sensors
(Rogowsky coils) on the circuit-breaker itself, one 40/1 A closed-core toroidal TA and a -MU undervoltage release for relay-controlled opening
(6)
at 12 and 17.5 kV and at 630 A rated current, the rated short-time withstand current is 20 kA for 1 second
H
L
D
Summary of Contents for HD4/R
Page 2: ......
Page 21: ...21 7 9 Overall dimensions 7 9 1 Fixed HD4 R 12 24 kV 630 1250 A TN 7237 Figure 9 ...
Page 22: ...22 7 9 2 Fixed HD4 R 12 24 kV 630 1250 A TN 7234 Figure 10 ...
Page 24: ...24 7 9 4 Plug in HD4 S 12 24 kV 630 1250 A TN 7236 Figure 12 ...
Page 25: ...25 7 9 5 HD4 Uniair 12 24 kV 630 1250 A TN 7235 Figure 13 ...
Page 26: ...26 7 9 6 HD4 Uniair F 12 24 kV 630 A TN 7275 Figure 14 ...
Page 27: ...27 7 9 7 HD4 Uniair 2R 12 24 kV 630 1250 A TN 7274 Figure 15 ...
Page 28: ...28 7 9 8 HD4 Uniair A 12 24 kV 630 1250 A TN 7273 Figure 16 ...
Page 29: ...29 7 9 9 HD4 UniMix F 12 24 kV 630 1250 A TN 7366 Figure 17 ...
Page 30: ...30 7 9 10 HD4 R SEC 12 24 kV 630 800 A 1VCD003536 Figure 18 ...
Page 37: ......