Page 76
© Copyright 2023 ABB. All rights reserved.
GPS2436_MAN
Rev. 1.3
Output NE100AC24ATEZ (Continued)
6,000W maximum
Output Current
1,
2
110Adc maximum from
-
40°C to +45°C 85Adc at +60°C
60Adc at +70°C 47.5Adc at +75°C
Rectifier self
-
derates at approximately
1.5 amperes per degree C (+45°C to +60°C)
2.5 amperes per degree C (+60°C to +75°C)
Float/Boost Voltage
42
-
58Vdc
Total Harmonic Distortion
<5% at Nominal Vac and >50Adc
Regulation
±0.5%
Ripple
100 mVrms
Noise
< 2mV psophometric
Current Limit Set Point
30A
-
110A
Mechanical
Width
5.25 in. (133.35 mm)
Height
8 in. (203.2 mm)
Depth
19.75 in. (501.65 mm)
Weight
20 lbs. (9 kg)
Environmental
Efficiency
> 90% typical
Heat Release
NE100AC24ATEZ
52Vdc, 40A
52Vdc, 50A
54.5Vdc, 40A
54.5Vdc, 50A
55Vdc, 55A
NE100AC24ATEZTEZ
52Vdc, 80A
52Vdc, 100A
54.5Vdc, 80A
54.5Vdc, 100A
54.5Vdc, 110A
Per rectifier:
231W [788.9 BTU/hr]
288W [983 BTU/hr]
242W [827 BTU/hr]
302W [1,030 BTU/hr]
332W [1,133 BTU/hr]
463W [1,578 BTU/hr]
577W [1,966 BTU/hr]
485W [1,654 BTU/hr]
605W [2,060 BTU/hr]
666W [2,266 BTU/hr]
Storage Relative Humidity
5% to 90%
Audible Noise
< 52dBA
EMC
EN 50022, level B, conducted and radiated (CISPR 22)
Standards Compliance
Safety Standard
EN 60950 (IEC950)
Certification Marks
UL, VDE, CE
Rectifiers are individually UL Recognized and/or CSA Certified to UL1950 and CSA
C22.2 No 234/950. Rectifiers are also approved to IEC
-
950/EN60950 by an EC
Notified
Body and have outputs classified as SELV.