GAA330-M
EMISSION MONITORING SYSTEM | OI/GAA330-M-EN REV. C
39
Terminal block –X1
1
Supply for heating sleeve of filter unit, 230 VAC, 50 to 60 Hz, 250 W, to
be fused by the customer with 6 A, regulation required!
2
Supply for sample gas line, 230 VAC, 50 to 60 Hz, 90 W/m,
max. 11 kW / 17 kW, to be fused by the customer with 16 A / 25 A,
regulation required! (optional)
3
Supply for heating of the probe tube, 230 VAC, 50 to 60 Hz,
max. 800 W, to be fused by the customer with 6 A, regulation required!
4
Supply for anti-frost heater, 230 VAC, 50 to 60 Hz, 300 W, to be fused
by the customer with 6 A
5
Supply for PTC elements and power supply unit -G02 / heated solenoid
valve in the sample gas outlet, 230 VAC, 50 to 60 Hz, 250 W, to be fused
by the customer with 6 A
-B01
Temperature limiter (set at 30 °C)
-E1
Heating sleeve of filter unit
-E2
Heated sample gas line
-E3
Heated probe tube
-E4
Anti-frost heater
-E5
Heated check valve
-T01
Power supply unit
Terminal block –X2
6
Supply for solenoid valve -Y1 cleaning filter surface and probe tube,
230 VAC, 50 to 60 Hz, 8 W, to be fused by the customer with 1 A
7
Supply for solenoid valve -Y2 cleaning filter, 230 VAC, 50 to 60 Hz, 8 W,
to be fused by the customer with 1 A
8
Supply for relay -K05 for the activation of cutoff valve -Y5, 230 VAC,
50 to 60 Hz, to be fused by the customer with 1 A
-K05
Relay
-Y1
Solenoid valve cleaning filter surface and probe tube
-Y2
Solenoid valve cleaning filter
-Y5
Cutoff valve
Terminal block –X3
9
Resistance thermometer Pt100 for filter unit of sample gas outlet
10
Resistance thermometer Pt100 for sample gas line
11
Resistance thermometer Pt100 for probe tube
12
Resistance thermometer Pt100 for filter unit of sample gas outlet
(fail-safe circuit)
13
Resistance thermometer Pt100 for sample gas line (fail-safe circuit)
14
Resistance thermometer Pt100 for probe tube (fail-safe circuit)