410 Parameters
Manual_Safebus
The FSO module expects an external STO
acknowledgement signal either from a digital
input or from the safety fieldbus after the
STO, SSE or SS1 request has been
removed and the stop function is completed
(output defined by parameter
is active).
STO.11 STO input A
Sets the digital input that is connected to the
primary input of the STO function.
None
No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
DI X113:3
Single input X113:3
DI X113:4
Single input X113:4
DI X114:1
Single input X114:1
DI X114:2
Single input X114:2
DI X114:3
Single input X114:3
DI X114:4
Single input X114:4
STO.12 STO input B
Sets the digital input that is connected to the
secondary input of the STO function. The
secondary input is mostly used for the
cascade connection.
See parameters
and
.
None
No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
DI X113:3
Single input X113:3
DI X113:4
Single input X113:4
DI X114:1
Single input X114:1
DI X114:2
Single input X114:2
DI X114:3
Single input X114:3
DI X114:4
Single input X114:4
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...