442 Parameters
SAFEIO.12 Cascade A
Sets the cascade connection A for the FSO
module. For each FSO module in cascade
A, the digital input connected to the safety
function is also internally connected to the
corresponding digital output of the FSO
module (digital input -> digital output). This
resembles a master/follower connection.
See section
on page
None
Not cascaded
X113:1 & X114:1 ->
X113:7 & X114:7
Redundant cascade X113:1 & X114:1 ->
X113:7 & X114:7
X113:2 & X114:2 ->
X113:8 & X114:8
Redundant cascade X113:2 & X114:2 ->
X113:8 & X114:8
X113:3 & X114:3 ->
X113:9 & X114:9
Redundant cascade X113:3 & X114:3 ->
X113:9 & X114:9
X113:1 -> X113:7
Single cascade X113:1 -> X113:7
X113:2 -> X113:8
Single cascade X113:2 -> X113:8
X113:3 -> X113:9
Single cascade X113:3 -> X113:9
X114:1 -> X114:7
Single cascade X114:1 -> X114:7
X114:2 -> X114:8
Single cascade X114:2 -> X114:8
X114:3 -> X114:9
Single cascade X114:3 -> X114:9
SAFEIO.13 Cascade B
Sets the cascade connection B for the FSO
module.
For each FSO module in cascade
B, the digital input connected to the safety
function is also internally connected to the
corresponding digital output of the FSO
module (digital input -> digital output).
See section
on page
None
Not cascaded
X113:1 & X114:1 ->
X113:7 & X114:7
Redundant cascade X113:1 & X114:1 ->
X113:7 & X114:7
X113:2 & X114:2 ->
X113:8 & X114:8
Redundant cascade X113:2 & X114:2 ->
X113:8 & X114:8
X113:3 & X114:3 ->
X113:9 & X114:9
Redundant cascade X113:3 & X114:3 ->
X113:9 & X114:9
X113:1 -> X113:7
Single cascade X113:1 -> X113:7
X113:2 -> X113:8
Single cascade X113:2 -> X113:8
X113:3 -> X113:9
Single cascade X113:3 -> X113:9
X114:1 -> X114:7
Single cascade X114:1 -> X114:7
X114:2 -> X114:8
Single cascade X114:2 -> X114:8
X114:3 -> X114:9
Single cascade X114:3 -> X114:9
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...