374 Technical data
Speed estimation
Ambient conditions
Speed range
Allowed range depends on the used motor.
Maximum range: (-30000…+30000 rpm)/(number of motor pole
pairs).
Accuracy
The speed estimation error is ± motor slip.
With synchronous motors, there can be small estimation ripples
at the zero speed region (below 10 rpm).
Operational frequency
Drive output up to 500 Hz
Operation
installed for
stationary use
Storage
in the protective
package
Transportation
in the protective
package
Altitude
0…1000 m
(0…3300 ft) above
sea level, no derating
required
1000…2000 m
(3300…6600 ft)
above sea level, air
outside the module
derated to
-15…+49 °C
(+5…+120 °F)
2000…4000 m
(6600…13200 ft)
above sea level, air
outside the module
derated to
-15…+40 °C
(+5…+104 °F)
-
-
Air temperature
-15…+70 °C
(+5…+158 °F)
-40…+70 °C
(-40…+158 °F)
-40…+70 °C
(-40…+158 °F)
Relative humidity
5…95%, no condensation allowed. If corrosive gases are present,
the maximum allowed humidity is 60%.
Contamination levels
IEC 60721-3-x
No contaminants, conductive dust or corrosive dust allowed.
Use at least IP54 enclosure in an environment where conductive
dust or corrosive dust exists.
- Chemical gases
Class 3C2
Class 1C2
Class 2C2
- Solid particles
Class 3S2. No
conductive dust
allowed.
Class 1S3
Class 2S2
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...