Configuration 283
How to fine-tune when zero speed limits are detected
Example 1
: Zero speed limit in reached in the SS1 function (and SSE with
emergency ramp), the SBC is not used.
=
20 ms
.
Example 2
: Zero speed limit in reached in the SS1 function (and SSE with
emergency ramp), a negative SBC delay (parameter
configured in the STO function:
=
20 ms
.
Note
: If the SBC delay (parameter
) is positive or zero
(
0 ms
), the SBC and STO functions are activated at the same time.
Time
Speed
Zero speed
limit reached
= 90 rpm
Mute time elapsed, STO activated
= 20 ms
Time
Speed
Zero speed
limit reached
= 90 rpm
Mute time elapsed, SBC activated
= 20 ms
SBC delay elapsed, STO activated
= -15 ms