260 Configuration
How to configure SLSn with ramp monitoring
Example:
The figure below shows an example of the SLS2 function with ramp
monitoring set-up:
• SLS2 function activated (
=
Version 1
)
• monitored deceleration ramp
SLS activation monitoring method
Ramp
)
• deceleration ramp and monitoring limits according SAR1 parameters (see section
on page
• automatic acknowledgement (
=
Automatic
)
• redundant SLS activation button connected to input
=
DI X113:2 & X114:2
)
• single output connected (
=
DO X114:7
)
• positive limits: SLS 1200.0 rpm, trip limit 1320.0 rpm
=
1200 rpm,
=
1320 rpm
).
• negative limits: SLS -900.0 rpm, trip limit -1020.0 rpm
=
-900 rpm,
-1020 rpm
).
• See also section
.
Note
: The difference between the SLS limit and the corresponding SLS trip limit must
be at least 0.1 rpm.
Note
: If you also use the SMS function, the SLS trip limits positive and negative must
be below the speed defined by parameter
and above the speed
defined by parameter
, respectively.