Section B
Messages and Hints
B-20
Level of the message
buffer for reacquisition
after overflow
This number defines the nominal level of the message list after an over-
flow. After an overflow has occurred, entries in the message list are de-
leted in accordance with a positive-displacement algorithm. This is re-
peated until the level within the message list corresponds to the value
stated here.
The positive-displacement algorithm is composed of the following steps:
1) Deletion of hint messages.
2) Deletion of active, acknowledged messages. First the oldest message
is deleted and then more recent messages are deleted consecutively.
Deletion begins with priority level 4 and continues consecutively to
priority level 0.
3) Deletion of the oldest inactive, unacknowledged message. Otherwise
the same as
2)
.
4) Deletion of the oldest active, unacknowledged message. Otherwise
the same as
2)
.
B 5.1 Tab Display
Message list
Display of
Selecting
Value
or
Long text
specifies the output format of a message in
the message list at the control station.
Formats
A choice of two display formats is available for fault and switch messages:
Value
Sound
Priority
Time Plant
area
Tag
name
S-Text
ST-Text
M-value,
Dim.
Type Date
Long
Sound
Priority
Time Plant
area
Tag
name
S-Text
L-Text
ST-Text
Date
System messages have a fixed display format
System
message
Sound
Group
Time
Plant
area
Tag
name
Fault text
Abbreviations:
Sound
Label identifying messages connected with a configured sound file. For
system messages this field is empty.
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
Summary of Contents for Freelance 2000
Page 1: ...EngineerIT Control Builder F Engineering Manual Freelance 2000 Operator Station Configuration ...
Page 4: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 12: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 14: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 20: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 22: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 46: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 48: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 76: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 190: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 192: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 218: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 226: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...