Section D
Graphic Display
D-61
D 5.22 Button, button field, radio button
→
Animate
→
Button, Button field
or
Radio buttons
,
→
Top left-hand corner of the button is positioned with a mouse click,
→
Define button size by moving the mouse, finish by clicking mouse button,
→
Parameter window entries,
→
Display the button with a frame.
These buttons can cause displays or faceplates to be called up, variables to be set to preset
numeric values, messages to be acknowledged or states to be displayed.
All the
buttons
,
button fields
and
radio button fields
can be displayed in a
variety of different formats (rectangle, rectangle with rounded corners, 3D-
rectangle, ellipse).
When a button is configured, either text can be specified for the button or any
static graphic object can be defined as the button symbol. For each separate
button, the text or button symbol, as well as the text and button colors are
specified in the button/radio button configuration. The size, orientation and font for
the text can be set or changed separately from the definition of button parameters
using the text attribute settings.
A
button press
under DigiVis does not require any additional confirmation, and can
write a process variable or call up a faceplate or display. A button can be linked with
any variable and displayed as either pushed or unpushed, as well as in different
pairs of colors.
A
button field
consists of one or more buttons with an associated confirm button. When
entering the parameters, the confirm button is always automatically displayed alongside. A
button field can comprise up to 25 separate buttons. The buttons in a button field can be
configured completely independently of one another. By pressing a button under DigiVis, a
value can be entered or a faceplate or display called up. The action is not actually performed
until the confirm button is pressed.
All the keys in a
radio button field
are linked with the same process variable. A value for this
variable can be pre-set for each key. When one of these keys is pressed under DigiVis, the value
configured is written to the process variable. If the process variable is set to one of the configured
values, this can be displayed on the corresponding key. Radio buttons cannot call up faceplates
or graphics, and do not have a confirm button.
Changing the text attributes of a button, button field or radio buttons:
→
Select button (or button field or radio field),
→
Change
→
Text attributes
or via toolbox
→
T
EXT
,
→
Enter or change text displays
→
accept with OK,
→
Button text appears as it was entered.
di0548.bmp
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
Summary of Contents for Freelance 2000
Page 1: ...EngineerIT Control Builder F Engineering Manual Freelance 2000 Operator Station Configuration ...
Page 4: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 12: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 14: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 20: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 22: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 46: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 48: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 76: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 190: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 192: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 218: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...
Page 226: ...Gross Automation 1725 South Johnson Road New Berlin WI 53146 www ssacsales com 800 349 5827 ...