Enclosed (IP22) filters
1
50 mm
(1.97 in.)
50 mm
(1.97 in.)
FOCH0320-52
1
50 mm
(1.97 in.)
50 mm
(1.97 in.)
FOCH0320-72
Space for cabling
1
■
Clearance
Non-enclosed (IP00) filters
•
The distance between the enclosure and the filter coil must be at least 15 mm
(0.59 in.).
•
The distance between the enclosure and the input/output terminals must be at
least 15 mm (0.59 in.).
•
The distance between the input busbars (if in use instead of cabling) and the filter
coil must be at least 15 mm (0.59 in.).
Enclosed (IP22) filters
The distance between the input/output cabling and the filter coil must be at least 50
mm (1.97 in.).
■
Cooling
The filters are designed to cool by natural convection. Ensure that there is enough
fresh cooling air available and that the hot air can freely escape from the filter enclosure
or cubicle. The air space above the non-enclosed (IP00) filter and the outlet air of the
enclosed (IP22) filter is hot [up to 70 °C (158 °F) depending on the installation and
operating conditions]. Take this into account in the installation.
20 Installation
4
Summary of Contents for FOCH
Page 1: ...OPTIONS FOR ABB DRIVES FOCH filters Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 16: ...16...
Page 22: ...FOCH0320 52 22 Installation...
Page 24: ...Installation illustrations of an enclosed IP22 filter FOCH0320 52 FOCH0320 52 24 Installation...
Page 26: ...26...
Page 32: ...FOCH0260 70 32 Dimension drawings...
Page 33: ...FOCH0320 50 FOCH0610 70 and FOCH0875 70 Dimension drawings 33...
Page 34: ...FOCH0260 72 34 Dimension drawings...
Page 35: ...FOCH0320 52 Dimension drawings 35...
Page 36: ...36...