Alternative mounting position
Recommended mounting position
1
2
1
2
Input terminals
2
Output terminals
1
■
Mounting plate
Non-enclosed (IP00) filters must be mounted on a grounded metal plate or cabinet
frame. Enclosed (IP22) filters can be installed to a wall without any grounded metal
plate. The structure must be of non-flammable material and strong enough to carry
the weight of the unit.
■
Encasing
Non-enclosed (IP00) filters must be encased or placed in a cabinet according to the
local safety requirements.
■
Electrical connections
•
Busbars are recommended for connections to the input terminals of non-enclosed
(IP00) filters.
•
Cables are recommended for connections to the input terminals of enclosed (IP22)
filters.
Cables must be protected for at least 105 °C (221 °F). If the filter is not installed in the
same cabinet as the drive, shielded symmetrical cable must be used between the drive
cabinet and the filter enclosure.
■
Free space
Free space is required around the filter for cooling as follows. The distances apply to
natural convection. With forced cooling, less free space is required.
18 Installation
4
Summary of Contents for FOCH
Page 1: ...OPTIONS FOR ABB DRIVES FOCH filters Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 16: ...16...
Page 22: ...FOCH0320 52 22 Installation...
Page 24: ...Installation illustrations of an enclosed IP22 filter FOCH0320 52 FOCH0320 52 24 Installation...
Page 26: ...26...
Page 32: ...FOCH0260 70 32 Dimension drawings...
Page 33: ...FOCH0320 50 FOCH0610 70 and FOCH0875 70 Dimension drawings 33...
Page 34: ...FOCH0260 72 34 Dimension drawings...
Page 35: ...FOCH0320 52 Dimension drawings 35...
Page 36: ...36...