Sensyflow FMT200-ECO2
THERMAL MASS FLOWMETER | OI/FMT200-ECO2-EN REV. H
11
Digital output
Can be configured as pulse / frequency outputs or binary
outputs.
Figure 6: Connection example
The digital output offers a 24 V HIGH signal or a 0 V LOW signal.
The output can be wired as active or passive.
Digital output (passive)
Pin / color
3+ (green) / 8- (red)
U
max
24 V DC
I
max
−
20 mA
f
max
2500 Hz
The output current must be limited to -20 mA in LOW state to guarantee an
output voltage U
a
< 2.5 V.
Digital output (active)
Pin / color
3+ (green) /
8− (red)
I
max
1 mA
f
max
2500 Hz
The output current must be limited to 1 mA in HIGH state to guarantee an
output voltage U
a
> 15 V.
Communication
RS 232
Pin / color
TxD: 2 (brown) /
RxD: 6 (pink) / GND: 8− (red)
Baud rate
9600 bits/sec.
Stop bits
1
Parity
None
Data bits
8
Parameterize
The Sensyflow FMT200-ECO2 can simultaneously operate one
analog output (current 0 / 4 to 20 mA or voltage 0 to 5 / 10 V),
one digital output (frequency, pulse, alarm) and a serial RS 232
interface.
Parameterization of the measuring system can also take place
via the serial interface. Using a PC or laptop, you can change the
output signal used or the adjust the settings of the measuring
ranges and signals.
The parameterization program is included in the standard scope
of delivery. A service and parameterization box is optionally
available for easier connection of the SensyFlow FMT200-ECO2
in the test field. That way, the various input and output variables
can be read out quickly and easily.
1
Power supply
2
Polarity reversal protection
3
Analog outputs
4
Digital output (pulse/freq)
5
Connector for Sensyflow FMT200-
ECO2
6
Connector for PC, Laptop
Figure 7: Service and parameterization box