Installation
25
Note:
The DIP switches are OFF by default. Turn them ON only if
an encoder that specifically needs a pull-up or pull-down resistor
is used.
The configuration of the DIP switches is shown in the table below:
Encoder type
1
2
3
4
Resistors
connected
Notes
Differential push-pull
off
off
off
off
no
Default setting
Single-ended push-pull
off
off
off
off
no
Default setting
Open collector (sinking)
on
on
on
off
yes
Resistors pull up
(A+, B+, Z+)
Open emitter
on
on
on
on
yes
Resistors pull down
(A+, B+, Z+)