F, V, W Series
Electromagnetic flowmeters
|
Full-bore flow sensors
3 Electrical Installation
16
OI/FEF/FEV/FEW–EN Rev. D
3.2.2 Sensor Cable Connections (Remote AquaMaster 3 Transmitter Only)
Caution.
Twist the three screen wires together and sleeve them.
Keep cable pairs twisted.
Make connections only as shown.
Maintain Environmental Protection at all times.
Conduit connections must provide cable entry sealing.
Fig. 3.11 Sensor Cable Connections – AquaMaster 3 Transmitter
Drain / Screen
to Internal Earth
for NPT Gland
Cut cables to
60 mm (2.35 in)
7 Violet
6 Blue
5 Green
4 Yellow
3 Orange
2 Red
1 Brown
Drain / Screen Wire for M20 Gland