ABB FAM3200 Series Manual Download Page 7

 

FAM3200

 ARMORED VARIABLE AREA PURGEMETER  |  CI/FAM3200-EN REV. D 

7

 

  

 

 

5

 

Installation 

 

Safety instructions 

 

 

 

 WARNING 

Risk of injury due to process conditions. 

The process conditions, for example high pressures and 
temperatures, toxic and aggressive measuring media, can 
give rise to hazards when working on the device. 
•  Before working on the device, make sure that the process 

conditions do not pose any hazards. 

•  If necessary, wear suited personal protective equipment 

when working on the device. 

•  Depressurize and empty the device / piping, allow to cool 

and purge if necessary. 

 

 

Installation conditions 

 

General 

The following points are to be considered during installation: 

•  The metal cone variable area flowmeter is installed 

vertically in a piping. The measuring media must flow 
from bottom to top. 

•  Keep the device as far away as possible from pipe 

vibrations. Fastening the piping is normally sufficient. 

•  Keep the device as far away as possible from powerful 

magnetic fields. Magnetic fields that are required for 
operating reasons must not influence the measurement 
result. 

•  The nominal diameter of the piping should be the same 

as the connection nominal diameter. 

•  Inlet and outlet sections are not required. Valves and pipe 

bends can be screwed on directly. 

•  Avoid pulsating flows and sudden pressure surges. 
•  Use valves which open slowly. 
•  If the flowmeter is installed in a pipeline where 

decommissioning is impossible or inexpedient, a bypass 
line should be provided. 

•  For gaseous measuring media, the flowmeter should be 

installed as close as possible to the pipe constrictions. 
The nominal diameter of the piping at the outlet of the 
flowmeter should be measured as small as possible.  

•  Stop and throttle valves should preferably be attached to 

the outlet of the flowmeter. 

•  For liquid measuring media, the nominal diameter of the 

piping should be dimensioned as large as possible (if 
economically viable). 

 

 

 

 

 

1

  Stop valve in the inlet 

2

  Flowmeter 

3

  Stop valve in the outlet 

4

  Bypass line 

Figure 4:  Installation of the flowmeter 

 

 

Installation recommendations 

Refer to VDI / VDE Directive 3513 sheet 3, Selection and 
Installation Recommendations for Variable Area Flowmeters. 
 

 

Pressure chambers and collecting tanks 

If piston pumps or compressors are used for the transport of the 
measuring media, a pulsating flow of the measurement media 
must be expected. 
In order to reduce the pulsating of the float, the installation of 
pressure chambers or collecting tanks in the piping before the 
flowmeter is recommended. 
 

 

Sensor insulation 

 

If the flowmeter needs to be insulated, only the meter tube must 
be included in the pipe insulation. The indicator housing must 
not be insulated. 
This prevents the temperature in the device from rising beyond 
permitted limits. 
 

 

Summary of Contents for FAM3200 Series

Page 1: ...le Area Purgemeter Measurement made easy FAM3200 Introduction Armored variable area purgemeters for measuring small flows of gases and liquids Additional Information Additional documentation on FAM320...

Page 2: ...s 8 Pressure loss 8 Prevention of compression oscillations when measuring gases 8 Pressure shocks 8 Solids content in the measuring medium 9 Mounting 9 General information 9 Flowmeter installation 9 6...

Page 3: ...he product may only be performed if expressly permitted by these instructions Information and symbols on the product must be observed These may not be removed and must be fully legible at all times Th...

Page 4: ...measuring media may only be used if the operator is able to perform regular and suitable tests to ensure the safe condition of the device The operator bears sole responsibility for the use of the devi...

Page 5: ...follower system 6 Cable entry Figure 1 Setup example The devices are used for local indication of the current flow rate with integrated alarm signalling units as flow rate monitors or with differenti...

Page 6: ...he shipper without delay and before installation Transport The center of gravity of some devices is not at the center of the equipment Use any of the available attachment points on the device for tran...

Page 7: ...and sudden pressure surges Use valves which open slowly If the flowmeter is installed in a pipeline where decommissioning is impossible or inexpedient a bypass line should be provided For gaseous mea...

Page 8: ...ntion of compression oscillations when measuring gases During low flow amounts and low operating pressure so called compression oscillations of the float can occur If the maximum upstream pressure lis...

Page 9: ...installation Install the flowmeter centrally in the piping at the required position using the correct threaded connections When tightening the process connections on the flowmeter use a spanner of the...

Page 10: ...position transmitter in two wire technology Other cable lengths available on request 7 Commissioning CAUTION Risk of burns due to hot measuring media The device surface temperature may exceed 70 C 158...

Page 11: ...s Repair and maintenance activities may only be performed by authorized customer service personnel When replacing or repairing individual components use original spare parts Note Spare parts can be or...

Page 12: ...s conditions The process conditions for example high pressures and temperatures toxic and aggressive measuring media can give rise to hazards when dismantling the device If necessary wear suited perso...

Page 13: ...Material load Figure 7 PS pressure TS temperature Maximum permissible operating pressure The permissible operating pressure is dependent on the optional device equipment Model Option Max permissible o...

Page 14: ...0 7 10 15 1 0 14 5 8 0 12 04H 6 1 59 230 8 12 18 18 0 7 10 15 1 0 14 5 8 0 12 05H 10 2 64 350 12 36 18 18 0 7 10 15 1 0 14 5 8 0 12 06H 16 4 23 540 19 07 18 18 0 7 10 15 1 0 14 5 8 0 12 07H 25 6 6 850...

Page 15: ...4 0 58 02 0 3 4 35 85 1 23 31H 600 158 5 18000 635 66 8 8 4 0 58 02 0 3 4 35 95 1 38 32H 700 184 92 21000 5547 61 8 8 4 0 58 02 0 3 4 35 105 1 53 33H 800 211 34 24000 847 55 8 8 4 0 58 02 0 3 4 35 13...

Page 16: ...mentation declarations of conformity and certificates are available in ABB s download area www abb com flow Trademarks Buna N is a registered trademark of DuPont Dow Elastomers Kalrez and Kalrez Spect...

Page 17: ...Company Address Contact person Telephone Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threa...

Page 18: ...18 FAM3200 ARMORED VARIABLE AREA PURGEMETER CI FAM3200 EN REV D Notes...

Page 19: ...FAM3200 ARMORED VARIABLE AREA PURGEMETER CI FAM3200 EN REV D 19 Notes...

Page 20: ...ice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reser...

Reviews: