Revision:
Language: Page:
A EN
14/28
1KHW001495-EN
C.12 V.11
ports
The V.11 ports are tested on correct settings and bit errors using data test equipment.
1. Check the port settings in the configuration (
Configuration / Data port to modem
assignment
) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test (recommended number of bits to transmit:
≥
10
6
).
C.12.1
V.11 Port 1
If used, perform a BER test as described above.
C.12.2
V.11 Port 2
If used, perform a BER test as described above.
C.13 V.24
ports
The V.24 ports are tested on correct settings and bit errors using data test equipment.
1. Check the port settings in the configuration (
Configuration / Data port to modem
assignment
) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test (recommended number of bits to transmit:
≥
10
6
).
C.13.1
V.24 Port 1
If used, perform a BER test as described above.
C.13.2
V.24 Port 2
If used, perform a BER test as described above.
C.13.3
V.24 Port 3
If used, perform a BER test as described above.
C.13.4
V.24 Port 4
If used, perform a BER test as described above.
C.13.5
V.24 Port 5
If used, perform a BER test as described above.
C.13.6
V.24 Port 6
If used, perform a BER test as described above.
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......