Remote Terminal Unit with GSM Communication 

 

 

User Manual 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 02-0333-01

Page 1: ...ComTroll 333 RTU Remote Terminal Unit with GSM Communication User Manual ...

Page 2: ...arts of this documentation may be reproduced in any form by any means without the written permission of Nortroll AS Copyright 2012 Nortroll AS All rights reserved All Nortroll products are trademarks or registered trademarks of Nortroll AS Other product names are trademarks or registered trademarks of their respective holders 2012 NORTROLL AS P O Box 133 7601 Levanger Norway www nortroll no ...

Page 3: ...U standard 15 COMMANDS AND STATUS MESSAGES 16 Request status 16 Commanding a new switch position and the auxiliary relays 16 Request configuration command 17 Resetting the password back to default 17 STATUS MESSAGE DEFINITION 17 Example Sending status request message from a cellphone 18 Example Receiving a message from the ComTroll 333 19 SENDING COMMANDS BY SMS 19 INSTALLATION IN NETTROLL 20 The ...

Page 4: ...rcuit indicators and line protection equipment ComTroll333 communicates with the SCADA system through the ComTroll 120 GSM LON Router using GSM Data CSD or SMS NorTroll offers a complete SCADA solution with NetTroll MicroSCADA Plug in module for configuration control monitoring and automation of the ComTroll 333 Terminals System overview GSM Data SMS GPRS ComTroll 120 GLR ComTroll Radio BaseStatio...

Page 5: ...the configuration properties first and incorporates a select before execute algorithm Commands e g OPEN CLOSE Switch can only be done from the same number programmed as the receiver number in the RTU Any attempt to control from any other numbers will be discarded even if the password is correct The ComTroll 333 RTU will periodically send its analog and digital status in a configurable time interva...

Page 6: ...ween CPU and GSM Module OFF Flash Green X X X Good GSM signal OFF Flash Red Gr X X X Medium GSM signal OFF Flash Red X X X Bad or no GSM signal X X ON X X sending receiving GSM Data or SMS X X X ON OFF Switch position is CLOSED X X X OFF ON Switch position is OPEN X ON X X X Mode selector is in Local position X X X Disable Disable Mode selector is in Remote position The OPEN and CLOSE indications ...

Page 7: ...on message are sent Local Command buttons The command buttons Open and Close are activated only when Mode Switch is in the LOCAL mode The buttons must be pressed more than 1 sec to execute the OPEN or CLOSE command The new status will be reported back to the central unit either as a SMS or CSD connection dependent upon the configuration setting Hardware Setup Preparing the SIM Card The PIN code mu...

Page 8: ...Outputs ERROR NETWORK BUSY OFF REMOTE LOCAL CLOSE OPEN Ai_1 4 5 2 3 4xAnalog inputs Settings ON 4 20mA OFF 0 10V 1 Low Battery Input 2 Analog Input 4 3 Analog Input 3 4 Analog Input 2 5 Analog Input 1 6 GND 1 Digital Input 1 2 Digital Input 2 3 Digital Input 3 4 Digital Input 4 5 Digital Input 5 6 Digital Input 6 7 OPEN 8 CLOSED 9 Input Common 1 2 3 4 5 6 7 8 9 1 Relay 5a 2 Relay 5b 3 Relay 6a 4 R...

Page 9: ...s a digital input that activates a warning message when the input is shorted to GND Please note that an external voltage relay must be used as this is a digital input This can also be used to monitor charging failure by connecting a voltage relay with a signal contact to this input The Low Battery warning is always sent as an SMS to the central unit To avoid warnings upon short voltage drops the S...

Page 10: ...t external secondary equipment on the MODBUS protocol Please note that not all versions of the ComTroll 333 RTU have this feature implemented in software Please contact NORTROLL AS for details 7 12Vdc supply for the powering the ComTroll 333 RTU MAX 15Vdc 3 Functional Description Configuration There are several parameters that need to be set before the ComTroll 333 RTU can be put into operation Se...

Page 11: ...arm or message on both activation and deactivation of the input 0 1 and 1 0 When there is a short pulse that activates the input the deactivation message must be switched off sending on 0 1 transitions only Default is 0 1 Command Set receiver phone number Description Defines which phone number the device will use when sending alarms and messages The phone number can be maximum 14 characters long A...

Page 12: ...from 1 0 CharB Send messages on SMS 1 SMS 0 DialUp CharC Allow SMS Control 0 Disable 1 Enable CharD Send two or four analog values 0 2 1 4 CharE Future Options NOTE All 5 characters must be sent Format Password 1 EDCBA T Normal response 3 1 EDCBA 1 T Error response 3 1 0 0 T Recommendations for configuration settings The default configuration setting is EDCBA 00000 In most cases a message on bot a...

Page 13: ...ariable 0000 means heartbeat is switched OFF Default value is 0072 hours Format Password 2 TIME T Normal response 3 2 TIME 1 T Error response 3 2 0 0 T Change the default password Default password is 1234 Command Set new password Description ComTroll 333 RTU will set the new password The new password will be made effective immediately An error will be returned if the CmT333 RTU is unable to extrac...

Page 14: ... must always be entered K 3 SOT timer Should not be changed without support from Nortroll Set with 5 char in millisec where only the seconds are used e g 07345 7 sec K 4 SELECT Timer Set with 1 3 characters in seconds in the range of 5 180 sec Default 35 sec Format Password 4 K XXXXX T Normal response 3 4 K xxxxx 1 T Error response 3 4 K xxxxx 0 T Deactivate individual Inputs It is possible to dea...

Page 15: ...l not send alarms upon status change DEFAULT VALUE 00000000 HGFEDCBA Format Password 7 HGFEDCBA T Normal response 3 1 HGFEDCBA 1 T Error response 3 1 0 0 T ITU standard Different network providers uses different ITU standards in the in the interface between the communication module and the network ComTroll 333 RTU can be set to use V 32 and V 110 Default setting V 32 Please refer to the local netw...

Page 16: ...us on digital inputs internal mode status and the analog inputs Format Password 5 T Normal response Two analog inputs A Status1 Status2 Analog1 Analog2 T Normal response Four analog inputs A Status1 Status2 Analog1 Analog2 Analog3 Analog4 T Error response N A Commanding a new switch position and the auxiliary relays Command COMMAND Switch and Relays Description Commands the actuator relays and the...

Page 17: ...OPEN CLOSE relays T2 1000ms Relay time out for relay 3 to 8 T3 10s SOT timer T4 35s Select timer RSSI xxxdBm Signal level in dBm Resetting the password back to default If the password for the device is changed and it is necessary to change it back to its default value 1234 send the following command to the device NORTXX The password will be set back to 1234 The command must be sent from a cell pho...

Page 18: ...is done in NetTroll When all four analog inputs are activated the string follows the same structure as shown above Raw value 0 to 1024 Status 1 and Status2 is a decimal number based on the following table BitNo ComTroll 333 Bit 0 Switch is Closed Bit 1 Switch is OPEN Bit 2 Remote Bit 3 Local Bit 4 Not used 0 Bit 5 Not used 0 Bit 6 Not used 0 Bit 7 SELECTED Bit 8 Di_1 Bit 9 Di_2 Bit 10 Di_3 Bit 11 ...

Page 19: ...ecute any critical operations such as OPEN CLOSE by SMS This software version requires NetTroll 4 1 or later Please note that commands will only be executed if the telephone number from where the command is sent is programmed as the receiver number in the RTU Before a command OPEN or CLOSE is sent to the RTU a Select SMS must be sent first see the list of commands in the commands and indications c...

Page 20: ...from NetTroll to GSM and vice versa The GSM LON Router The ComTroll 120 GLR must be installed before any GSM Devices can be added into NetTroll Database This unit is installed in the same way as other devices using the LonWorks technology e g ComTroll 155 RTU with radio communication Detailed information about the ComTroll 120 GLR can be found in separate documentation All ComTroll GSM field devic...

Page 21: ...tween 1 and 9999 Install the first RTU with NodeID 1 the next NodeID 2 and so on The information typed in the window above will be stored in the NetTroll Database Upon installation of a new device the default password 1234 must always be used Select the Device Type you have created for this device The default Device Type is ComTroll 333 RTU 4Ai 4Ai four analog inputs ...

Page 22: ...crease response time The receiver phone number should always be entered using the country code No information is sent to the ComTroll 333 RTU device from this window The device will appear as a new device in the network view the selected name as identifier Setting the Device Properties Select the device name you are about to configure Enter the Advanced Tab 1 Set GLR Phone Number Type the telephon...

Page 23: ... X X 1 X SMS alarms when Di_1 to Di_6 changes X X 0 X X Disable SMS Control of switchgear status X X 1 X X Enable SMS Control of switchgear status X 0 X X X Use 2 analog inputs X 1 X X X Use 4 analog inputs 3 Set Actuator relay timeout Different types of actuators and switches require different relay timeout Please set a value appropriate for the switchgear to which your ComTroll 333 RTU is connec...

Page 24: ...ssage within a specified time interval If NetTroll is missing two consecutive heartbeats an alarm will be raised The heartbeat can be switched OFF by setting 0000 hours 4 characters must always be sent The example below gives a heartbeat message every 6th 24 hour period Default heartbeat is 72hours 5 Change password The default password should be changed to a user defined password before installin...

Page 25: ...ct Channel Select which analog Input 1 4 the settings will be done for In the above example it is Analog Input 1 Conversion Use always Linear Raw Value Range Use always 2 byte unsigned integer Low value 0 and high value 1023 Scaled Value Range Data type should always be 4 byte real number Low the displayed value when the raw value received from the RTU is 0 High the displayed value when the raw va...

Page 26: ...tting analog input properties in NetTroll refer to the NetTroll manual and Release Notes Device configuration The device configuration in NetTroll allows the user to set specific massages and message properties for each installed ComTroll 333 RTU device These settings are only local settings in NetTroll and the settings are not sent to the RTU device but are only stored in the database ...

Page 27: ...tinue uploading default values Then all message texts and alarm properties can be set for each individual device For details about these settings please refer to the NetTroll 4 0 4 1 Release Notes documents When more than one ComTroll 333 RTU device shall have the same configuration settings can be copied from a device with the desirable settings Using the Another device selection all settings wil...

Page 28: ...0 1800 1900 MHz Inputs Open and close status from the end contacts of the switchgear 6 general optic isolated digital inputs 4 analog inputs 0 10V or 4 20mA Maximum input voltage 50V dc Outputs Open and close of the switchgear Operated remotely or locally 6 user specified Normally Open relays Maximum switching voltage current 200V 1A AC DC Power supply Min 10Vdc Max 15Vdc Power Consumption 8mA in ...

Page 29: ... 02 0120 00 ComTroll 120 GLR Router Kit for NetTroll Product nr 15 7540 51 NetTroll 4 1 MicroSCADA Software Product nr 15 7500 04 NetAlert 3 5 SMS Alarm Module w GSM modem Product nr 15 7500 40 NetTRoll SCADA Gateway NORTROLL AS Postboks 133 N 7601 Levanger Norway Phone 47 7408 5500 Fax 47 7408 5501 Email nortroll nortroll no ...