156 Commissioning instructions
Manual Energy Storage Inverter ESI-S
Table 54: Possible inverter unit addresses and corresponding DIP switch settings (facing the
board with ABB logo at the top), counting low to high.
Inverter
address
DIP switch 1
setting (ID0)
DIP switch 2
setting (ID1)
DIP switch 3 setting (ID2)
1
Low
Low
Low
2
High
Low
Low
3
Low
High
Low
4
High
High
Low
Notes:
−
Do not use other settings than the ones mentioned in the table
−
It is recommended to assign increasing addresses starting from the main master
at the left and moving right
−
Assigning the same address to different units in one system will lead to the
system not being able to start up and go in error (Bad Ratings)
When a system consists of more than one unit, attention has to be paid to the proper
termination of the communication bus between the different units. This communication
bus is depicted in the below
by the black lines interconnecting the different
units.
Control board in the ‘previous’ unit
Control board in the ‘next’ unit
From previous unit (if present)
To next unit (if present)
Figure 81: Communication bus between different units
In order to terminate the bus correctly, the fourth switch (counting from left to right)
from DIP switch 22 (Cf.
) has to be set as follows:
−
High: For the first unit in a system (single unit or first physical unit of a multi-unit
inverter)
−
High: For the last physical unit of a multi-unit inverter
−
Low: For all the other units