ABB EQmatic
Commissioning
42 2CDC512090D0202 | QA/S x.yy.1
2. Register mapping
To configure a new register mapping, open the
Management > Meter > Register mapping
menu
and add a new register mapping using the "
+ Add
" button.
Normally you will find the register mapping for the data points in the technical data or in the
manufacturer's description for the related device.
Example for Modbus mapping from a data sheet:
Data point
Start register
address
Size (number of registers)
Resolution
Unit
Data type
Active energy
0x5000
4
0.01
Kwh
Unsigned
Power
0x6000
2
0.01
W
Unsigned
Voltage L1
0x7000
2
0.1
V
Unsigned
Product name
0x7500
6
-
-
String
Serial number
0x8500
4
-
-
Unsigned
Add to the parameters in the window the specific information for the register mapping (e.g. register
mapping name: ABB EQ meters) and save the settings.
Note
Several versions of a register mapping can exist or be added.