3.9.2. Network frequency
This area allows you to enter the frequency of the installation: 50Hz or 60Hz.
Selection of this parameter allows the protection release to calibrate its protection and measurement functions according to the
value chosen by the user.
3.9.3. Modules
PR332/P and PR333/P allow 4 internal modules to be connected and their settings configured.
The following options are available upon access to the Settings-Modules menu:
- 3 menus dedicated to modules PR330/V (MEASURING Module menu), PR330/D-M (COM Module), S51/P1 (SIGNALLING
Module). The menus are available once the modules have been correctly connected and installed.
- Menu for setting the presence/absence of a unit on the Local Bis. Enabling activates a presence monitoring function regarding
a unit on the local bus so as to ascertain whether the connection is correct and to signal any communication alarms.
All the details are given in the chapters with the characteristics of internal modules PR120/V, PR120/D-M, Contact S51/P1.
3.9.4. Datalogger
PR322/P and PR333/P support the Dataloggger storage function. On accessing the Settings-Datalogger menu, the operator can
edit all the parameters of the function and enable or inhibit recording in the manual mode. More details in par. 1.8.3.
3.9.5. Dual Set
PR333/P allows the user to enable the double protection function. All the parameters of the function can be enabled and edited
on access to the Settings-Dual Set menu. More details in par. 1.6.19.
3.9.6. Measurement Interval
The storage time for the measurements log file can be adjusted in the Settings-Measurement Interval menu. Further details about
the measurements function are given in par. 1.7.4.
3.9.7. Harmonic distortion
The harmonic distortion monitoring function can be activated in the Settings-Harmonic Dist. menu: if activated and if the value
is more thann 2.1, a fault will be signalled on the display.
3.9.8. System
The date and time of the protection release, the Language and Password can be adjusted in the Settings-System menu.
3.9.8.1.
Language
When selecting the system language, make sure that:
- The protection release is in the local mode (if PR330/D-M is installed);
- the CB is open;
- Vaux 24Vdc and/or busbar voltage by means of PR330/V and/or PR030/B are present.
The protection release will not allow the language to be changed in the absence of one of the above conditions.
3.9.8.2.
Password
PPR332/P and PR333/P are supplied with the default password: 0001.
The password, which is required if all the changes to the protections or settings in the protection release are to be saved, can be
changed in the Settings-System-New Password menu.
The values that can be used in the password range from 0000 to 9999. The default password is given in par. 1.13.
To change the PW, first enter the old one, then select the 4 new figures: the value of each figure can be chosen with the UP and
DOWN keys. Use ENTER to confirm the figure and pass on to the next one.
The password is checked after the fourth figure has been entered. The procedure will change from the “READ” state to the “EDIT”
state if the password is correct.
The password prompt is disabled by setting the value of the password to [0000] (in the “System Configuration” menu). It is
therefore always possible to switch from “READ” to “EDIT”.
WARNING: The password is valid for up to two minutes from the last time a key was pressed. After that time, it
must be entered again so as to validate any changes or to access the menus.