![ABB EIB Delta User Manual Download Page 5](http://html.mh-extra.com/html/abb/eib-delta/eib-delta_user-manual_4388005.webp)
EIB Delta-Meter
Electricity Meters
4
ABB i-bus
®
EIB
Environmental conditions:
Mechanical data:
Display:
EIB connection:
Standards/norms:
Ambient temperature:
– 5° C ... + 45° C
Storage temperature:
– 40° C ... + 70° C
Relative humidity:
< 75% annual average,
95% max. 30 days/year
Housing material:
– Front window and housing
Polycarbonate
– Terminal area
Glass-fibre-reinforced polycarbonate
Dimensions (H x W x D):
96 x 122.5 x 64.8 mm
Protection class:
II
Resistance to heat and fire:
Equivalent to IEC 695-2-1
Protection against penetration
Equivalent to IEC 529
of dust and water:
Test voltage:
Output/housing
⇔
earth
2 kV, 50 Hz / min
Type of protection acc.
to DIN VDE 0100:
– with long terminal cover
IP51
– with short terminal cover
IP20
Cable cross-section:
– Transformer rated meter
max. 10 mm
2
– Direct connected meter
max. 25 mm
2
Weight:
0.6 kg
LCD display:
7-digit, height of figures: 7 mm
LED indicator:
– Transformer rated meter
Red LED, 1000 Imp/kWh (kvarh)
– Direct connected meter
Red LED, 5000 Imp/kWh (kvarh)
Communication protocol:
ABB i-bus
®
EIB
(European Installation Bus)
Number of bus devices:
max. 64 per line
(total of over 14,000 possible)
Transmission medium:
Twisted twin-core cable,
YCYM or J-Y(St)Y 2x2x0.8 mm
Cable lengths:
– Total length of a line
≤
1000 m
– Between two devices
≤
700 m
– Between power supply
≤
350 m
and device
EMC:
Between meter and EIB terminals
– Surge voltage
6 kV, 1.2/50 µs (IEC 255-4)
– Burst
4 kV, 5/50 ns (IEC 801-4)
Operating and display elements:
– ABB i-bus
®
‚ EIB terminal
Bus connection terminal, supplied
– Red LED and push button
For entering the physical address
Active energy meter, class 1 and 2:
IEC 1036
Reactive energy meter, class 2:
IEC 1268
ABB i-bus
®
‚ EIB:
EIBA hand book, release 3.0
PTB approval number:
20.15 98.80