40
EBN853 / EBN861
ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C
… 11 Repair
Fuses
Type
Fuse
Installation location
Design
Rated current of fuse
at 115 V AC
at 230 V AC
EBN853
External fuse
External
–
16 A, time-lag
16 A, time-lag
Mains fuse
Connection area
G-fuse cartridge
5 × 20 mm
12.5 A, time-lag
10 A, time-lag
Analog input
Connection area
G-fuse cartridge
5 × 20 mm
40 mA, fast-acting
40 mA, fast-acting
Brake fuse
Power supply board
G-fuse cartridge
5 × 20 mm
0.315 A, medium time-lag 0.315 A, medium time-lag
DC link fuse
Power supply board
G-fuse cartridge
6.3 × 32 mm
10 A, super fast-acting
10 A, super fast-acting
Heater (optional)
Connection area
G-fuse cartridge
5 × 20 mm
2 A, time-lag
2 A, time-lag
EBN861
External fuse*
External
Safety fuse / thermal
circuit breaker
–
35 A / 16 A
Brake fuse
Power supply board
G-fuse cartridge
5 × 20 mm
–
0.315 A, medium time-lag
DC link fuse
Power supply board
G-fuse cartridge
6.3 × 32 mm
–
16 A, super fast-acting
Fuse for binary outputs (3x)
Connection area
G-fuse cartridge
5 × 20 mm
–
0.2 A, medium time-lag
Heater (optional)
Connection area
G-fuse cartridge
5 × 20 mm
2 A, time-lag
2 A, time-lag
* The 35 A safety fuse and the 16 A thermal circuit breaker are included in the scope of delivery. The conductor cross-section between the fuse and the electronic
system must be at least 2.5 mm
2
(14 AWG).