EBN853 / EBN861
ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C
27
Electrical data for inputs and outputs
Power supply
EBN853
Supply voltage (standard actuators)
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
Supply voltage (Ex actuators)
115 V AC (94 to 127 V) or 230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Current consumption at the electronic unit
(AC 115 V / AC 230 V)
Actuator
l
max
at 115 V
l
max
at 230 V
l
pos
(115 V + 230 V):
approx. 40 to 50 % of l
max
RHD(E)250-10
1.8 A
0.9 A
RHD(E)500-10
2.2 A
1.1 A
RHD(E)800-10
5.0 A
2.5 A
RHD(E)1250-12
5.0 A
2.5 A
RHD(E)2500-25
5.0 A
2.5 A
RHD(E)4000-40
5.8 A
2.7 A
RHD(E)8000-80
5.0 A
2.5 A
RSD(E)10-5,0
2.2 A
1.1 A
RSD(E)10-10,0
3.6 A
1.8 A
RSD(E)20-5,0
3.6 A
1.8 A
RSD(E)20-7,5
4.8 A
2.4 A
RSD(E)50-3,0
5.0 A
2.5 A
RSD100-1.5
5.0 A
2.5 A
RSD200-0.7
5.0 A
2.5 A
External fuse for electronic unit
16 A; time-lag
EBN861
Supply voltage (standard actuators)
230 V AC (190 to 260 V); 47.5 63 Hz; single-phase
Supply voltage (Ex actuators)
230 V AC (190 to 253 V); 47.5 63 Hz; single-phase
Current consumption at the electronic unit
(AC 230 V)
Actuator
l
max
at 230 V
l
pos
(230 V): approx. 40 to 50 % of l
max
RHD(E)2500-10
5.3 A
RHD(E)4000-10
10.0 A
RHD8000-12
8.0 A
RHDE8000-15
8.0 A
RHD(E)16000-30
12.5 A
RSD(E)50-10
6.4 A
RSD100-10.0
12.5 A
RSD200-5.0
13.0 A
External fuse for electronic unit
Safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA); fuses are in the scope of delivery