Serial Communication – EFB
FLN Protocol Technical Data
Overview
The FLN fieldbus connection to the ACH550 drives is based on an industry standard
RS-485 physical interface. The FLN (Floor Level Network) Fieldbus protocol is a
serial communication protocol, used by the Siemens APOGEE® system. The
ACH550 interface is specified in Siemens application 2734.
Supported Features
The ACH550 supports all required FLN features.
Reports
The ACH550 provides seven pre-defined reports. Using a report request generated
from the FLN fieldbus controller, select one of the following sets of points. By
providing views of selected points, these reports are often easier to work with than
views of the full point database.
ABB ACH550
Startup
FLN ABB ACH550 Report
Point
Subpoint Name
Data
#
Type
01
LAO
CTLR ADDRESS
Each host FLN application (e.g. CIS or Insight) controls
both the particular data reported for each point, and the
report format.
02
LAO
APPLICATION
20
LAO
OVRD TIME
29
LDO
DAY.NIGHT
FLN Startup Report
Point
Subpoint Name
Data
#
Type
21
LDI
FWD.REV
Each host FLN application (e.g. CIS or Insight) controls
both the particular data reported for each point, and the
report format.
22
LDO
CMD FWD.REV
23
LDI
STOP.RUN
24
LDO
CMD STP.STRT
25
LDI
EXT1.2 ACT
26
LDO
EXT1.2 CMD
34
LDI
ENA.DIS ACT
35
LDO
ENA.DIS CMD
36
LDI
FLN LOC ACT
60
LAO
INPUT REF1
61
LAO
INPUT REF2
68
LDO
FLN LOC CTL
69
LDO
FLN LOC REF