ABB Distribution Protection Unit 1500R
5-19
Interfacing with the Relay
website:www.abb.com/papd
9/99
Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected)
Function
Setting
Range
Step Size
Default
51P
Curve Selection
See Table 1-1
Extremely Inverse
Pickup Amps
1 to 12 A or 0.2 to 2.4 A
0.1 or 0.02
6.0 or 1.2
Time Dial/Delay
1.0 to 10.0
5.00
50P-1
Curve Selection
See Table 1-3 or Disable
Standard
Pickup X 51P
0.5 to 20 times 51P pickup setting
0.1
3.00
Time Dial/Delay
See Table 1-3
-
50P-2
Selection
Disable or Enable
Disable
Pickup X 51P
0.5 to 20 times 51P pickup setting
0.1
-
Time Delay
0 to 9.99 seconds
0.01
-
50P-3
Selection
Disable or Enable
Disable
Pickup X 51P
0.5 to 20 times 51P pickup setting
0.1
-
46
Curve Selection
See Table 1-10 or Disable
Disable
Pickup Amps
1 to 12 A or 0.2 to 2.4 A
0.1 or 0.02
-
Time Dial/Delay
See Table 1-10
-
51N
Curve Selection
See Table 1-2 or Disable
Extremely Inverse
Pickup Amps
1 to 12 A or 0.2 to 2.4 A
0.1 or 0.02
6.0 or 1.2
Time Dial/Delay
See Table 1-2
5.00
50N-1
Curve Selection
See Table 1-6 or Disable
Standard
Pickup X 51N
0.5 to 20 times 51N pickup setting
0.1
3.00
Time Dial/Delay
See Table 1-6
-
50N-2
Selection
Disable or Enable
Disable
Pickup X 51N
0.5 to 20 times 51N pickup setting
0.1
-
Time Delay
0 to 9.99 seconds
0.01
-
(3I>)
(3I>>1)
(3I>>2)
(3I>>3)
(insc>)
(IN>)
(IN>>1)
(IN>>2)