ABB DLMU Series Selection Manual Download Page 4

Voltage

Monitors

7.4 

Low Voltage Products & Systems 

1TRC 001 009 C0202 

ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com

Description

The WVM Series provides protection against premature equipment (motor) failure caused by voltage faults on 
the 3 Phase Line.  The WVM’s microcontroller design provides reliable protection even if regenerated voltages 
are present.  It combines dependable fault sensing with a 10 fault memory and a 6 LED status display.  Part 
instrument, part control, the WVM protects your equipment when you’re not there and displays what happened 
when you return.  The WVM is fully adjustable and includes time delays to prevent nuisance tripping and 
improve system operation.  Time delays include a 0.25 to 30 s adjustable trip delay, an adjustable 0.25 to 64 
m (in 3 ranges) restart delay, plus a unique 3 to 15 s true random start delay.  The random start delay prevents 
voltage sags caused by simultaneous restarting of numerous motor loads after a power outage.

Operation

The output relay is energized when all conditions 

are acceptable and the WVM is reset.  A restart 

and/or random start delay may occur before the 

output relay is energized.

 Protects Against: Phase 

  Loss & Reversal; Over, 
  Under & Unbalanced 
  Voltages; Short Cycling

 10 Fault Memory & Status

  Displayed on 6 LED Readout

 Switch Selectable Automatic  

  Restart, Delayed Automatic  
   Restart, & Manual Reset 

 Isolated 10 A SPDT Relay

  Contacts

Approvals: 

3 Phase Voltage Monitor

WVM Series
Motor Protector

Example P/Ns:

 WVM

X

6

 - 200 ... 240 V AC

8

 - 355 ... 425 V AC

9

 - 400 ... 480 V AC

0

 - 500 ... 600 V AC

  3 Phase Line Voltage

X

- 2 ... 10%

X

- 0.25 ... 30 s

Unbalance   Trip Delay

X

A

 - Switch Selectable:

 

 Automatic Restart Upon Fault Trip

R

 - Switch Selectable:

 

 Automatic Restart Upon  Fault 

  Correction

X

L

 - 0.25 ...   64 s

N

 -     6 ... 300 s

H

 - 0.25 ...  64 m

  Reset Method

  Restart Delay

WVM011AL,

WVM911AL-60 

(No Random Restart Delay) 

Field  Adjustment:     

Select  the  line  voltage  listed 

on the motor’s name plate.  This automatically sets 

the over and under voltage trip points.  Consult the 

equipment’s  manufacturer  specifications  for  the 

correct trip delay, unbalance percentage, and restart/

reset operation and restart delay.  Make connection 

to all three line phases as shown in the connection 

diagram.  Apply power.  If the relay fails to energize, 

view the LEDs for the cause, and correct the problem.  

If  the  phase  sequence  is  incorrect,  swap  any  two 

wires.  No further adjustment should be required to 

achieve maximum equipment protection.

Read  Memory: 

  Fault(s)  stored  in  the  memory 

are indicated when the yellow LED is flashing.  To 

read memory, rotate selector from Manual to Read 

Memory.  The last fault will be displayed.  Repeat this 

operation to read the second to the last fault.  Repeat 

until up to 10 faults are noted.

  Memory Reset: 

  To  clear the  memory  of all  

  faults stored, rotate selector to Clear Memory 

  for 5 seconds.  The yellow LED will turn off.

  Memory Overload:

  The 11th fault causes the  

  first to be removed from memory.  Only the 10  

  most recent faults are retained.

Random Start Delay:

  A new 3 to 15 s random start 

delay is selected by the microcontroller  when a fault 

is corrected and when the operating voltage (L1, L2, 

L3) is applied to the WVM.  A random start delay does 

not occur when the reset is manual.

Automatic Restart:

  Upon fault correction, the output 

will re-energize after a random start delay.

Automatic Restart Upon Fault Trip: 

 When a fault is 

sensed for the full trip delay, the output de- energizes 

and a restart  delay is initiated.  This delay locks out 

the output for the delay period.  Should the fault be 

corrected by the end of the restart delay, the output 

will re-energize after a random start delay.  A restart 

delay will also occur when operating voltage (L1, L2, 

L3) is applied to the WVM.

Manual Reset: 

 After a fault condition is corrected, 

the  WVM  can  be  manually  reset.    There  are  two 

methods; a customer supplied remote switch, or the 

onboard selector switch.

Manual Reset (Onboard): 

Rotate  selector  switch 

from the Manual  Reset  position to  Auto  Restart 

w/ Delay then back again to Manual Reset within 3 

seconds.  The output will immediately energize.

Remote  Reset:

      Reset  (Restart)  is  accomplished 

by a momentary contact closure across terminals 1 

& 2.  The output will immediately energize.  Remote 

switch requirements are 

 10 mA at 20 V DC and the 

reset terminals are not isolated from line voltage.  A 

resistance  of 

  20K

    across  terminals  1  &  2  will 

cause immediate automatic restart.

Automatic Restart Upon Fault Correction:

(P/N includes an 

R

)

 

 

When a fault is sensed for the full trip delay, the output 

relay de-energizes.  Upon correction of the fault, a 

restart delay begins.   At the end of this delay, the 

output will re-energize after a random start delay.  If 

a fault occurs during restart timing, the restart time 

delay will be reset to zero, and the output will not 

energize until the restart delay is completed.

-60  Option:    Add  the  suffix  -60  to  any  automatic 

restart  part  number  to  remove  the  Random  Start 

Delay feature.  See example P/N‘s below.

Connection

F = Fuses    

NO = Normally Open  

NC = Normally Closed

RS = Optional Remote Reset Switch

CAUTION: 

 

2 amp max fast acting 
fuses must be installed 
externally in series with 
each input. (3)  

  Series

Relay contacts are isolated.
Dashed lines are internal
connections.

 ASME A17.1 rule 210.6
 NEMA MG1 14:30, 14:35
 IEEE C62.41-1991 Level B  

ANSI Device #27/47/59

Listed

WVM02B01

 

12.13.06

 

Summary of Contents for DLMU Series

Page 1: ...Reversal WVM 7 4 DLMU 7 6 HLMU 7 8 PLMU 7 10 PLM 7 12 TVW 7 14 TVM 7 16 PLR 7 18 PLS 7 20 CM MPS CM PAS CM PSS CM PVS CM PFS CM PFE CM PVE CM PBE Note Product pages are not included in this catalog Go to www ssac com s7 pdf Click on the Product Name ie CM MPS to open the catalog page Adobe Acrobat Reader is required HLV 7 22 KVM 7 25 CM ESS 1 see Note above CM ESS 2 see Note above CM EFS see Note ...

Page 2: ...Mounting w a w s w s w s w s w a w a w a Surface Mounting w s w s w s w s 8 Pin Plug In Screw Terminals Quick Connects Output DPDT Relay s SPDT Relay SPST NO Line V Connection Wired Phase to Phase Universal Voltage Phase to Neutral Single Phase Trip Point s Adjustable v Trip Point s Fixed Supply Voltage Required Protection Phase Loss Motor Operating Motor Start Up Only Undervoltage Overvoltage Unb...

Page 3: ... w a w a w a w a w a w a w a w a w a 8 Pin Plug In Screw Terminals Quick Connects Output DPDT Relay 2 SPDT ESS 2 SPDT Relay ESS 1 SPST NO 2 SPDT Independent Normal Status Energized Energized Energized Energized Energized Energized Energized Energized Selectable De energized Selectable Line V Connection Wired Phase to Phase 380 or 400 Universal Voltage 500VAC Max 200 500 208 440 Phase to Neutral Si...

Page 4: ...elector from Manual to Read Memory The last fault will be displayed Repeat this operation to read the second to the last fault Repeat until up to 10 faults are noted Memory Reset To clear the memory of all faults stored rotate selector to Clear Memory for 5 seconds The yellow LED will turn off Memory Overload The 11th fault causes the first to be removed from memory Only the 10 most recent faults ...

Page 5: ... 2 10 Trip Delay Adjustable from 0 25 30 s 15 Phase Loss 15 unbalance Response Time 200 ms Random Start Delay Range 3 15 s Reset Restart Delay Low Range 0 25 64 s 15 Normal Range 6 300 s 15 High Range 0 25 64 m 15 Fault Memory Type Nonvolatile RAM Capacity Stores last 10 faults Status Indicators 6 LEDs provide existing status memory readout Note 50 of operating line voltage must be applied to L1 L...

Page 6: ...on Delay Adjustable Unbalance Trip and Restart Delay DLMUBRAAA 200 480 V SPDT N O Restart Delay on fault correction Adjustable Unbalance Trip and Restart Delay DLMUCNAAN 200 480 V SPDT N C No Restart Delay Adjustable Unbalance and Trip Delay DLMUCL0420A 200 480 V SPDT N C Lockout Function 4 Unbalance 20 s Trip Delay Adjustable Restart Delay LED Operation The LED flashes green during the restart de...

Page 7: ...Frequency 4 Reset 3 50 or 60 Hz Phase Sequence A B C L1 L2 L3 Response Time Phase Reversal Phase Loss 200 ms Reset Automatic Output Type Isolated Electromechanical Relay Control Contact Form Single pole double throw SPDT 1 c o Rating 10 A resistive at 240 V AC 8 A resistive at 277 V AC N O 1 4 hp at 120 V AC 1 3 hp at 240 V AC Alarm Contact Form N O or N C SPST selected in part number Rating 2 A r...

Page 8: ...1 Level B Approvals Universal 3 Phase Voltage Monitor HLMU Series DPDT Motor Protector Connection 3 phase fuse block disconnect P N P0700 241 2 Amp Fuse P N P0600 11 CAUTION 2 amp max fast acting fuses are recommended to protect the equipment s wir ing They are not required to pro tect the HLMU Restart Function ANSI Device 27 47 59 Ordering Table Example P N A Adjustable 2 10 Fixed Specify Unbalan...

Page 9: ...e from 1 30 s or specify fixed delay 1 30 s in 1 s increments 15 Restart Delay Adjustable from 0 6 300 s if no restart delay is selected a 0 6 s initialization delay applies 15 Over Under Frequency 4 Reset 3 50 or 60 Hz Phase Sequence A B C L1 L2 L3 Response Time Phase Reversal Phase Loss 200 ms Reset Automatic Output Type Isolated Electromechanical Relay Form Double pole double throw DPDT Rating ...

Page 10: ...ection The output relay will not energize if a fault condition is sensed as three phase input voltage is applied Line voltage is selected with the knob setting the over and under voltage trip points Voltage range is automatically selected by the microcontroller See accessory pages for specifications Protects Against Phase Loss Phase Reversal Overvoltage Undervoltage Unbalanced Voltages Octal Plug ...

Page 11: ... Point 109 113 of adjusted line voltage Reset Voltage 2 of trip voltage Voltage Unbalance Trip Point Adjustable from 2 10 or fixed 4 10 Reset on Balance Selected Unbalance 2 3 4 5 6 7 8 9 10 Reset 1 5 2 5 3 5 4 5 5 4 6 3 7 2 8 1 9 Trip Delay Range Adj from 0 25 30 s or fixed 2 30 s 15 Severe Unbalance 2X Selected Unbalance 0 25 2 s disabled when the trip delay is less than 2 s Random Start Delay 0...

Page 12: ...ssory pages for specifications Protects Against Phase Loss Phase Reversal Undervoltage Unbalanced Voltages 8 Pin Plug in Base Adjustable Low Voltage Trip Point Factory Fixed Unbalance and Trip Delay Line Voltages 200 480 V AC in 3 Ranges SPDT Isolated 10 A Relay Contacts ASME A17 1 rule 210 6 NEMA MG1 14 30 14 35 IEEE C62 41 1991 Level B Approvals 3 Phase Voltage Monitor PLM Series Motor Protector...

Page 13: ...voltage Reset Voltage Plus 3 of trip voltage Voltage Unbalance Trip Unbalance Factory fixed from 4 8 Reset on Balance 0 7 unbalance typical Trip Delay Range Factory fixed from 2 20 s Tolerance 15 Phase Reversal and Phase Loss Response Time Phase Reversal 200 ms Phase Loss 200 ms Phase Loss 35 unbalance Reset Automatic Output Type Electromechanical relay Form Isolated single pole double throw SPDT ...

Page 14: ... SPDT Relay Contacts Bi color LED Indicator Shows Output Status Faults Time Delays Phase Reversal and Set Point ASME A17 1 rule 210 6 NEMA MG1 14 30 14 35 IEEE C62 41 1991 Level B Approvals Compact 3 Phase Voltage Monitor TVW Series The NetTM Motor Protector Connection Example P N Female quick connect P Ns P1015 13 AWG 10 12 P1015 64 AWG 14 16 P1015 14 AWG 18 22 3 phase fuse block disconnect P N F...

Page 15: ... V AC in 4 ranges 30 20 Line Frequency 50 100 Hz Phase Sequence ABC Power Consumption Approx 2 W for 240 V units Approx 3 W for 480 V units Overvoltage Undervoltage Voltage Unbalance Overvoltage Undervoltage Voltage detection with delay trip automatic reset Undervoltage Trip Point 88 92 of the selected line voltage Reset Voltage 3 of trip voltage Overvoltage Trip Point 109 113 of the selected line...

Page 16: ...Points and Delays Fixed Voltages from 208 480 V AC Isolated 10 A SPDT Relay Contacts Bi color LED Indicator Shows Output Status Faults Time Delays and Phase Reversal ASME A17 1 rule 210 6 NEMA MG1 14 30 14 35 IEEE C62 41 1991 Level B Approvals Compact 3 Phase Voltage Monitor TVM Series The NetTM Motor Protector Connection Example P N Female quick connect P Ns P1015 13 AWG 10 12 P1015 64 AWG 14 16 ...

Page 17: ...See Ordering Table Line Frequency 50 100 Hz Phase Sequence ABC Power Consumption Approx 2 W for 240 V units Approx 3 W for 480 V units Overvoltage Undervoltage Voltage Unbalance Overvoltage Undervoltage Voltage detection with delay trip automatic reset Undervoltage Trip Point 88 92 of the selected line voltage Reset Voltage 3 of trip voltage Overvoltage Trip Point 109 113 of the selected line volt...

Page 18: ...1 Level B Approvals 3 Phase Voltage Monitor PLR Series Motor Protector Connection Panel mount kit P N BZ1 Octal 8 pin socket P N OT08PC 3 phase fuse block disconnect P N P0700 241 2 AMP fuse P N P0600 11 DIN rail P Ns 017322005 Steel C103PM Al Relay contacts are isolated Dashed lines are internal connections Field Adjustment Turn the adjustment knob fully counterclockwise and apply three phase pow...

Page 19: ...AC 480 V AC 480 V AC 350 480 V AC 530 V AC Frequency 50 60 Hz Phase Sequence ABC Response Times Pull in 400 ms Drop out 100 ms Hysterisis Pull in Drop out 2 Output Type Electromechanical relay energized when all voltages are acceptable Form Single pole double throw SPDT Rating 5 A resistive at 240 V AC 1 4 Hp at 120 V AC Maximum Voltage 250 V AC Protection Surge IEEE C62 41 1991 Level B Isolation ...

Page 20: ... phase sequence is correct The output relay will not energize if the phases are reversed Reset is automatic upon correction of the fault See accessory pages for specifications Protects Against Phase Reversal Low Cost Protection One Unit for All Sized Motors 3 Wire Connection for Delta or Wye Systems Octal Base Connection Industry Standard Wiring SPDT Isolated Relay Contacts Factory Calibrated No A...

Page 21: ...30 V AC Frequency 50 60 Hz Phase Sequence ABC Response Times Pull in 300 ms Drop out 50 ms Output Type Electromechanical relay energized when the phase sequence is correct Form Isolated SPDT Rating 120 240 V AC 10 A resistive at 240 V AC 380 480 V AC 8 A resistive at 240 V AC 1 4 Hp at 120 V AC 500 to 530 V AC 5 A resistive at 240 V AC 1 4 Hp at 120 V AC Maximum Voltage 250 V AC Protection Isolati...

Page 22: ... N Relay contacts are non isolated Operation Mounting bracket P N P1023 6 NO Normally Open NC Normally Closed C Common T1 Undervoltage Trip Point T2 Restart Delay US Patent 6708135 Dashed lines are internal connections Upon application of input voltage the output relay re mains de energized When the input voltage value is above the pull in voltage the restart delay begins At the end of the restart...

Page 23: ...in 1 s increments Repeat Accuracy 0 5 or 20 ms whichever is greater Tolerance Factory Calibration 5 Reset Time 150 ms Time Delay vs Temp Voltage 10 Output Type Form Electromechanical relay SPDT Ratings SPDT N O SPDT N C General Purpose 125 240 V AC 30 A 15 A Resistive 125 240 V AC 30 A 15 A 28 V DC 20 A 10 A Motor Load 125 V AC 1 hp 1 4 hp 240 V AC 2 hp 1 hp Life Mechanical 1 x 106 Electrical 1 x ...

Page 24: ...Voltage M onitors 7 24 Low Voltage Products Systems 1TRC 001 009 C0202 ABB Inc 888 385 1221 Technical assistance 800 377 7722 www ssac com Notes ...

Page 25: ...23 20 DIN rail P N s 017322005 Steel 132 V AC 264 V AC Maximum Line Voltage Undervoltage Set Point Adjustable 78 99 V AC 156 199 V AC Part Number KVM4 KVM6 Inches Millimeters V Voltage L LED S Undervoltage Set Point NO Normally Open NC Normally Closed C Common Transfer Contact Dashed lines are internal connections Function TP Undervoltage Set Point R Reset Point Line Voltage Type Single Phase Inpu...

Page 26: ...RC001009C0202 Printed in USA January 2007 Technical Help and Product Support ABB Inc Telephone 315 638 1300 Technical Help 800 377 SSAC 7722 Fax 315 638 0333 http www ssac com Sales Information Canada ABB Inc 2105 32nd Avenue Lachine Quebec H8T 3J1 Canada Telephone Atlantic Quebec Region 800 567 0203 Ontario Region 866 460 3300 Mid West Pacific Region 866 222 8368 ...

Reviews: