![ABB DLMU Series Selection Manual Download Page 25](http://html.mh-extra.com/html/abb/dlmu-series/dlmu-series_selection-manual_4384025.webp)
Voltage
Monitors
Low Voltage Products & Systems
7.25
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
1TRC 001 009 C0202
Technical Data
Accessories
Description
The KVM Series is a single phase undervoltage monitor designed to protect sensitive equipment against
brownout undervoltage conditions. The compact design and encapsulated construction make the KVM an
excellent choice for OEM equipment.
Operation
The output relay is energized and the LED glows
green when the input voltage is above the reset
voltage threshold. If the input voltage drops below the
undervoltage set point, the output relay and LED will
de-energize. The output relay will remain de-energized
as long as the input voltage is below the reset voltage.
Reset is automatic when the input voltage returns to a
normal range.
See accessory pages for
specifications.
Mechanical View
Economical Single Phase
Brownout/Undervoltage
Protection
Isolated 8 A SPDT Relay
Contacts
Protects sensitive 110-120 V
AC or 220-240 V AC Loads
Adjustable Low Voltage Trip
Point
LED Indicator
Approvals:
KVM Series
Single Phase
Undervoltage Monitor
Connection
Female quick
connect
P/N:
P1015-64
(AWG 14/16)
Quick connect to
screw adaptor
P/N:
P1015-18
DIN rail adaptor
P/N:
P1023-20
→
DIN rail P/N‘s:
017322005
(Steel)
←
132 V AC
264 V AC
Maximum Line Voltage
Undervoltage Set Point (Adjustable)
78 ... 99 V AC
156 ... 199 V AC
Part Number
KVM4
KVM6
Inches (Millimeters)
V = Voltage L = LED S = Undervoltage Set Point
NO = Normally Open NC = Normally Closed
C = Common, Transfer Contact
Dashed lines are internal connections.
Function
TP = Undervoltage Set Point R = Reset Point
Line Voltage
Type
Single Phase
Input Voltage/Frequency
110 ... 120 V AC or 220 ... 240 V AC/50 ... 60 Hz
Power Consumption
2.5W at 132 V AC; 4.5W at 264 V AC
Power Off Reset Time
<
150 ms
Undervoltage Detection
Undervoltage Set Point KVM4
78 ... 99 V AC
KVM6
156 ... 199 V AC
Undervoltage Reset Point KVM4
Fixed at 104 V AC
KVM6
Fixed at 209 V AC
Repeatability
+/- 0.5% under fixed conditions
+/-1% over temperature range
Voltage Sensing Accuracy
+/-2% at 25°C
Output
Type/Form
Electromechanical Relay/SPDT
Rating
8 A resistive at 120 V AC, 1/3 hp at 120/240 V AC
Life
Mechanical; 1 x 10
6
; Electrical; 1x10
5
LED Indicator
Glows green when output energized
Protection
Surge
IEEE C62.41-1991 Level A
Circuitry
Encapsulated
Isolation Voltage
>
1500 V RMS Input to Output
Insulation Resistance
>
100 M
Ω
Minimum
Mechanical
Mounting
Surface mount with one #10 (M5 x 0.8) screw
Package
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Termination
0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage Temperature
-25 to +55°C/-40 to +85°C
Humidity
95% relative, non-condensing
Weight
2.6 oz (74 g)
KVM01B01
08.21.08