ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
7 Advanced Level
70
IM/CM/ED–EN Rev. X
…Profile Parameters / …Enter Program
Enter
S
egments
S
egment No.
Enter the segment number to be configured.
Type
Select the segment type as described below:
Soak
Maintains the setpoint at a constant value for the duration of the segment. A soak
segment requires the entry of the desired duration in hh:mm:ss.
If the soak segment is the 1st segment in a program the setpoint value will be set as
defined by the
SPT Start Condition
parameter. For other segments, the setpoint value
will be derived from the end setpoint value of the previous segment.
Ramp Rate
Increases or decreases the setpoint at a linear rate until the desired value is reached. A
Ramp Rate
segment requires the user to enter the desired end setpoint and the desired
ramp rate. The ramp rate is entered in engineering units per time period. The time period
is defined by the
Ramp Rate Units
parameter.
Ramp Time
Increases or decreases the setpoint at a linear rate until the desired value is reached. A
Ramp Time
segment requires the user to enter the desired end setpoint and the desired
ramp duration in hh:mm:ss.
Step
Changes the setpoint value from the end value to of the previous segment to a new
value. A
Step
segment requires the entry of the
Step
setpoint value.
Wait
Delays the program until a condition has been met as defined by either or both of the
Wait Event
digital signals.
Note
.
Ramp Rate
or
Ramp Time
will be displayed according to the setting of the
Ramp
Type
parameter in
Common Settings (see page 66)
.
End
Ends the program.
Period
Select the soak or ramp period of the segment in hhh:mm:ss.
Note
. Only displayed if
Segment Type
is configured as
Soak
or
Ramp
time.
S
etpoint
Select the required end setpoint value for the segment in engineering units.
Note
. Only displayed if the
Segment Type
is configured as
Ramp Rate
or
Ramp Time
.
Ramp Rate
Select the required
Ramp Rate
for the segment.
Note
. Only displayed if
Segment Type
is
Ramp Rate
.
Wait Events
Select the condition under which the
Wait
segment will delay the program. The segment
will enter a wait condition when the
Wait Event
digital inputs match the segment wait
condition as defined below.
Event 1
Waits on the event as defined by the
Wait Event 1
digital signal.
Event 2
Waits on the event as defined by the
Wait Event 2
digital signal.
Event 1 OR 2
Waits on the state of
Wait Event 1
OR
Wait Event 2
.
Event 1 AND 2
Waits on the state of
Wait Event 1
' AND
Wait Event 2
.
Note
. Displayed only if
Segment Type
is
Wait
.