ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
7 Advanced Level
68
IM/CM/ED–EN Rev. X
…Profile Parameters / …Common Settings
S
egment Options
G'teed Ramp/
S
oak
Enables the
Guaranteed Ramp/Soak
(
Holdback
) function. When enabled (
On
), the
relevant configuration frames are displayed in
Program
/
Segment
menus to allow the
Guaranteed Ramp/Soak
function to be configured.
Events 1 to 8
Enables the
Segment Event
function. When enabled (
On
), the relevant configuration
frame is displayed for each segment to allow the
Segment Events
to be configured.
PV Event
Enables the
PV Event
function. When enabled (
On
), the relevant configuration frames are
displayed in the
Program / Segment
menus to allow the
PV Event
to be configured.
Timed Event
Enables the
Timed Event
function. When enabled (
On
), the relevant configuration frames
are displayed for each segment to allow the
Timed Event
to be configured.
User Value
Enables the
User Value
function. When enabled (
On
), the relevant frames are displayed
to allow the
User Value
function to be configured.
Retort Function
Enables the
Retort
function. When enabled (
On
), the relevant frames are displayed to
configure the
Retort
function.
Continue
Continues to the next segment.
Repeat Segment
Repeats the current segment.
PV Event Trip
The
PV Event Trip
value used to determine the
PV Event
status for each segment. The
value is set in
PV
engineering units.
Note
. Available only if the
PV Event
functionality is enabled in the
Segment Options
menu.
User Value Limits
Default Value
The default value that the User Value will be set to when a program is not running.
Note
.
User Value
menu only available if the
User Value
functionality has been enabled in
the
Segment Options
menu.
Low Limit
The Low Limit parameter is used to set the minimum
User Value
value that may be
entered for each segment.
High Limit
The High Limit parameter is used to set the maximum
User Value
value that may be
entered for each segment.
Fast Run Mode
This frame enables a mode that allows the profile program to be run 8 times faster than
the programmed times. In this mode guaranteed
Ramp
/
Soak
settings are ignored but
wait conditions are not overridden.