ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
7 Advanced Level
IM/CM/ED–EN Rev. X
69
…Profile Parameters
Enter Program
Program No.
Select the program to be configured (1 – 30).
Name
Enter the
Program Name
(up to 16 characters) to be used to identify the running
program in the
Operator Page
display.
Repeat Count
Enter the number of times the program is to be repeated.
None
The program will not be repeated (it will run once).
1 … 10
The program repeats as defined, for example, if '1' is selected the program runs twice.
Continuous
The program runs continuously until stopped by the operator.
S
etpoint
S
tart/End
S
tart
The start setpoint value for the first segment of the program.
Note
. Available only if the
SPT Start Condition
parameter is set to
Program Setpoint
.
End
Defines the end condition of the program:
Local Setpoint
The program will enter the
Stop
state and switch to the currently selected
Local
Setpoint
.
Hold Setpoint
The program remains active and in control at the setpoint defined by the last segment. It
remains active until stopped, at which point the
Control Setpoint
switches to the current
Local Setpoint
.
Jump Program
At the end of the program, the profiler jumps to the start of another configured program.
Jump To Program
Define the next program that the profiler will jump to on completion of the current
program.
Note
. Available only if
Setpoint End
condition is set to
Jump Program
.
Holdback Hysteresis
Hysteresis values are used to hold the program when the process value deviates from
the setpoint by more than the hysteresis value as defined by the
Guaranteed Ramp
option for each segment.
Note
. Available only if
Guaranteed Ramp
is enabled.
S
oak
Set the hysteresis value applied to
Soak
segments.
Ramp
Set the hysteresis value applied to
Ramp
segments.