26
PME120-AI / PME120-AN (Contrac)
ELECTRICAL ROTARY ACTUATOR | SEI/PME120-EN REV. A
… 8 Electrical test values
Test values (Brake and Motor)
Brake voltage
DC 135 V with AC 115/AC230 V mains supply.
Motor voltage
Check for currents symmetry (i. e. with clip-on ammeter).
Winding resistance
Depending on the actuator version proceed as follows:
PME120-AI (integrated electronic unit)
A
Mains fuse
B
Spare fuse
C
Heater fuse
(only for 25 °C Version)
D
Fuse against active feed at 20 mA
setpoint input
Figure 36: Pin assignment
1. Remove the plug.
2. Remove the actuator hood with electronics.
3. Check pins at pin carrier,Refer to pin carrier in
Figure 36
.
Measuring points
Resistance
Winding resistance ±5 % at 20 °C (motor); pin. 6-7 / 7-8 / 6-8
3.4
Ω
Winding resistance ±5 % at 20 °C (brake); terminal 9-10
50
Ω
PME120-AN (separate electronic unit)
1. Remove plug.
2. Measure between pins at actuator plug, see
Electronic unit
EAN823 (Contrac) for PME120-AN
on page 18 and
Electronic
unit EAS822 (Contrac) for PME120-AN
on page 20 for pin
reference.
Measuring points
Resistance
Winding resistance ± 5 % at 20 °C (motor); pin. 1-2 / 2-3 / 1-3
3.4
Ω
Winding resistance ± 5 % at 20 °C (brake); terminal 9-10
50
Ω